Alpha Technologies XM2-300CE-HP User Manual

Page 18

Advertising
background image

1.2

XM2-300HP Layout, continued

1.2.2 Inverter Module Overview, continued

Battery Switch: The battery switch disconnects the battery from the inverter

module’s DC circuit. With the battery switch turned off, the XM2-300HP power supply

does not transfer to standby mode, the inverter is disabled, and the battery charger

cannot charge the battery.

Battery Input Connector The battery plugs directly into the inverter module’s battery

connector. The connector is polarized and fits in one direction only.

Temp Probe Connector: The Dual Remote Temperature Sensor (DRTS) plugs di-

rectly into the temperature probe (RJ-11C type) connector. One sensor clips onto the

front edge of the power supply shelf and monitors the ambient air temperature within

the enclosure. The second sensor attaches to the negative terminal of the battery

and monitors battery temperature. To install, connect the ring terminal onto the nega-

tive battery terminal as shown below.

Fig. 1-7, Inverter Module Connections

Temp Probe

Connector

Smart

Display

Battery Input

Connector

Always verify proper polarity of cables before connecting the battery to the power module. Polarity is clearly

marked for easy identification. Reversing the polarity prevents the battery from being active in the system.

NOTE:

Fig. 1-8, Temperature Probe Locations

18

017-877-B1-001 Rev. A