2.0

Installation, continued

2.5 Programming the PIM

Programmable parameters (with PIM option) are:
Channel 1 Overcurrent Limit: The RMS current level that causes the Output 1 protection

relay to trip after a specified delay (overcurrent tolerance period).
Channel 2 Overcurrent Limit: The RMS current level that causes the Output 2 protection

relay to trip after a specified delay (overcurrent tolerance period).
Retry Delay: The time between each attempt to restart an output in the event of an

overcurrent event.
Retry Limit: The number of times the XM2-300HP will attempt to restart an output

connection. Once the RETRY LIMIT is exceeded, the XM2-300HP will attempt to restart the

output connection every 30 minutes. Set this parameter to “zero” to disable the “automatic

retry” function.
Overcurrent Tolerance Period (1-10 seconds): In the event of an overcurrent episode,

the amount of time an output overcurrent condition is permitted on either output connection.

Once this time expires, the output protection relay disables its output feeder.
Reset Output 1/Reset Output 2: Once fault condition has been corrected, this manually

resets tripped output.

Programming any of the above parameters will reset the “trip/retry” counters.

NOTE:

If the optional PIM is not installed, the values shown on the “PIM PARAMETERS” line of the Smart Display

are “read only”.

NOTE:

27