6.0

Return and Repair Information, continued

6.1 Emergency Shutdown

The XM2-300HP contains more than one live circuit. During an emergency, utility power

can be disconnected at the service entrance or main electrical panel to protect emergency

personnel. However, power is still present at the output. To prevent the possibility of injury to

service or emergency personnel, always follow this procedure to safely shutdown the power

supply.
Emergency Shutdown Procedure:

STEP 1

:

Turn the battery switch to OFF.

STEP 2

:

Unplug the AC Input Line Cord from the service entrance.

STEP 3

:

Disconnect both the Output 1 and Output 2 connections.

3

2

1

59

017-877-B1-001 Rev. A