9 resumption of utility power – Alpha Technologies XM2-300CE-HP User Manual

Page 53

Advertising
background image

Before turning on the AC voltage input breaker, use a voltmeter to verify the input voltage

1.

is within specifications.

When the proper voltage is present, verify the battery voltage indicated on the Smart

2.

Display is greater than 10.5Vdc. Disconnect the power supply from the generator output

and plug the power supply input cord into the convenience outlet within the enclosure.

The power supply operates on battery backup for this short period of time, but exercise

caution during this changeover as the grounding circuit to the power supply is broken.
If the battery is at or below the low voltage cutoff, then the power supply will NOT trans-

fer to battery back up and there will be a momentary power outage to the cable system

while you make this changeover.
Turn on the AC input power.

3.

Shut down the generator and remove the grounding system.

4.

4.0

Operation, continued

4.9 Resumption of Utility Power

Use caution when disconnecting and reconnecting a generator to utility power. Dangerous

voltages are present.

Exercise care to ensure that both powering systems are

not connected at the same time, or

damage to the power supply and the generator may result.

CAUTION!

WARNING!

53

017-877-B1-001 Rev. A