IM-pAC Getting Started Guide

www.camcoindex.com | www.destaco.com

Issue Number: 5

5.2

Ground leakage

The ground leakage current depends upon the internal EMC filter being installed. The

drive is supplied with the filter installed. Instructions for removal of the internal EMC filter

are given in section 5.3.2 Removing the internal EMC filter .

With internal EMC filter installed

30μA DC (10MΩ internal bleed resistor, relevant where DC leakage current is being measured)
Size A

1 phase 110V drives

4mA AC at 110V, 50Hz (proportional to supply voltage and frequency)
1 phase 200V drives

10mA AC at 230V, 50Hz (proportional to supply voltage and frequency)

Size B and C

1 phase 200V drives

20mA AC at 230V, 50Hz (proportional to supply voltage and frequency)

3 phase 200V drives

8mA AC at 230V, 50Hz (proportional to supply voltage and frequency)

3 phase 400V drives

8.2mA AC at 415V, 50Hz (proportional to supply voltage and frequency)

Fuses/MCB
The AC supply to the drive must be installed with suitable protection against overload

and short circuits. Failure to observe this requirement will cause risk of fire.

WARNING

The drive must be grounded by a conductor sufficient to carry the prospective fault

current in the event of a fault. See also the warning in section 5.2 Ground leakage

relating to ground leakage current.

WARNING

To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified

tightening torques for the power and ground terminals. Refer to the table below.

WARNING

Frame size

Maximum power terminal screw torque

A

0.5 N m / 4.4 lb in

B and C

1.4 N m / 12.1 lb in

Braking resistor: High temperatures and overload protection
Braking resistors can reach high temperatures. Locate braking resistors so that damage

cannot result. Use cable having insulation capable of withstanding the high temperatures.
It is essential that the braking resistor be protected against overload caused by a failure

of the brake control. Unless the resistor has in-built protection, a circuit like those shown

in Figure 5-1 and Figure 5-2 should be used, where the thermal protection device

disconnects the AC supply to the drive. Do not use AC relay contacts directly in series

with the braking resistor circuit, because it carries DC.

WARNING

When connecting single phase to a dual rated 200V unit, use terminals L1 and L3.

NOTE

For control terminal connections, see Pr 05 on page 51.

NOTE

For information on the internal EMC filter, see section 5.3.1 Internal EMC filter .