Parameters

Parameters are grouped together into appropriate subsets as follows:
Level 1

Pr 01 to Pr 10: Basic drive set-up parameters

Level 2

Pr 11 to Pr 12: Drive operation set-up parameters

Pr 15 to Pr 21: Reference parameters

Pr 22 to Pr 29: Display / keypad configuration

Pr 30 to Pr 33: System configuration

Pr 34 to Pr 36: Drive user I/O configuration

Pr 37 to Pr 42: Motor configuration (non-standard set-up)

Pr 43 to Pr 44: Serial communications configuration

Pr 45:

Drive software version

Pr 46 to Pr 51: Mechanical brake configuration

Pr 52 to Pr 54: Fieldbus configuration

Pr 55 to Pr 58: Drive trip log

Pr 59 to Pr 60: PLC ladder programming configuration

Pr 61 to Pr 70: User definable parameter area

Level 3

Pr 71 to Pr 80: User definable parameter set-up

Pr 81 to Pr 95: Drive diagnostics parameters

These parameters can be used to optimise the set-up of the drive for the application.

7.1

Parameter descriptions - Level 1

Used to set the minimum speed at which the motor will run in both directions.

(0V reference or minimum scale current input represents the value in Pr 01)

Used to set the maximum speed at which the motor will run in both directions.
If Pr 02 is set below Pr 01, Pr 01 will be automatically set to the value of Pr 02. (+10V

reference or full scale current input represents the value in Pr 02)

Sets the acceleration and deceleration rate of the motor in both directions in seconds/

100Hz.

No

Function

Range

Defaults

Type

01

Minimum set speed

0 to Pr 02 Hz

0.0

RW

No

Function

Range

Defaults

Type

02

Maximum set speed

0 to 1500 Hz

60.0

RW

The output speed of the drive can exceed the value set in Pr 02 due to slip compensation

and current limits.

NOTE

No

Function

Range

Defaults

Type

03

Acceleration rate

0 to 3200.0 s/100Hz

0.1

RW

04

Deceleration rate

0.2

If one of the standard ramp modes is selected (see Pr 30 on page 60), the deceleration

rate could be extended automatically by the drive to prevent over voltage (OU) trips if the

load inertia is too high for the programmed deceleration rate.

NOTE