DE-STA-CO IM-pAC AC Drive Getting Started Guide User Manual

Page 61

Advertising
background image

IM-pAC Getting Started Guide

61

Issue Number: 5

www.camcoindex.com | www.destaco.com

Re

ad

Me
F

irs

t

Instr
ucti

on

s

Sa

fety
Info
rm

atio

n

R

ati

ng

D

ata

Me
ch

an

ica

l

Inst
al

lati

on

El

ec

tric

al

In

stal

la

tion
Ke

yp

ad

a

nd

Dis
pla

y

Pa
ram

e

te

rs

D

iag

no

stics

UL
Li

sti

ng

Info
rm

atio

n

measured, the drive may trip on OV and OI.AC while trying to catch a spinning motor.

dig

: Digital input

th

:

Motor thermistor input, connect as per diagram below

Fr

:

Frequency input.

Fr.hr

:High resolution frequency input.

Figure 7-11

Trip resistance: 3kΩ

Reset resistance 1k8

n=0

:

At zero speed

At.SP

: At speed

Lo.SP

: At minimum speed

hEAL

: Drive ok

Act

:

Drive active

ALAr

: General drive alarm

I.Lt

:

Current limit active

At.Ld

: At 100% load

USEr

: User programmable

Fr

:

Voltage proportional to motor speed

Ld

:

Voltage proportional to motor load

A

:

Voltage proportional to output current

Por

:

Voltage proportional to output power

USEr

: User programmable

No

Function

Range

Defaults

Type

34

Terminal B7 mode select

dig, th, Fr, Fr.hr

0:dig

RW

0V

Motor thermistor

input

T1

B7

If Pr 34 is set to th so that terminal B7 is used as a motor thermistor, the functionality of

terminal B7 as set-up with Pr 05, drive configuration, will be disabled.

When setting to th, press mode four times. Analog reference 2 will no longer be selected

as the speed reference. Analog reference 1 should be used.

NOTE

No

Function

Range

Defaults

Type

35

Digital output control (terminal B3)

n=0, At.SP, Lo.SP, hEAL,

Act, ALAr, I.Lt, At.Ld, USEr

0:n=0

RW

This parameter is automatically changed by the setting of Pr 12. When Pr 12

automatically controls the setting of this parameter, this parameter cannot be changed.

NOTE

A change to this parameter is only implemented if the drive is disabled, stopped or

tripped and the

STOP/RESET key is pressed for 1s.

NOTE

No

Function

Range

Defaults

Type

36

Analog output control (terminal B1)

Fr, Ld, A, Por, USEr

0:Fr

RW

A change to this parameter is only implemented if the drive is disabled, stopped or

tripped and the

STOP/RESET key is pressed for 1s.

NOTE