DE-STA-CO IM-pAC AC Drive Getting Started Guide User Manual

Page 62

Advertising
background image

62

IM-pAC Getting Started Guide

www.camcoindex.com | www.destaco.com

Issue Number: 5

3

:

3kHz

6

:

6kHz

12

: 12kHz

18

: 18kHz

0

: No autotune

1

: Non-rotating static autotune

2

: Rotating autotune

Enter the motor rated frequency (taken from the motor name plate).
Defines the voltage to frequency ratio applied to the motor.

Auto

: Automatically calculates the number of motor poles from the settings of Pr 07

and Pr 39

2P

:

Set for a 2 pole motor

4P

:

Set for a 4 pole motor

6P

:

Set for a 6 pole motor

8P

:

Set for an 8 pole motor

Ur S

: Stator resistance is measured each time the drive is enabled and run

Ur

:

No measurement is taken

Fd

:

Fixed boost

Ur A

: Stator resistance is measured the first time the drive is enabled and run

Ur I

:

Stator resistance measured at each power-up when the drive is enabled and run

SrE

:

Square law characteristic

In all Ur modes, the drive operates in open loop vector mode.

No

Function

Range

Defaults

Type

37

Maximum switching frequency

3, 6, 12, 18 kHz

12

RW

18kHz is not available on IM-pAC B and C sizes.

NOTE

No

Function

Range

Defaults

Type

38

Autotune

0 to 2

0

RW

Never Autotune

WARNING

No

Function

Range

Defaults

Type

39

Motor rated frequency

0.0 to 1500.0 Hz

60.0

RW

No

Function

Range

Defaults

Type

40

Number of motor poles

Auto, 2P, 4P, 6P, 8P

2:4 pole

RW

No

Function

Range

Defaults

Type

41

Voltage mode select

Ur S, Ur, Fd, Ur A, Ur l, SrE

2:Fd

RW

The drive default setting is Ur I mode which means that the drive will carry out an

autotune every time the drive is powered-up and enabled. If the load is not going to be

stationary when the drive is powered-up and enabled, then one of the other modes

should be selected. Not selecting another mode could result in poor motor performance

or OI.AC, It.AC or OV trips.

NOTE

Advertising