PAGE 8-12


enFORCE

Operation Manual

Code A8_6 - SERVO AMPLIFIER ERROR / INPUT VOLTAGE ABNORMAL

The SAN controller servo power supply circuit has detected improper input voltage either above
or below the specified limits.

CAUSE:
1. The controller internal power supply has failed.
2. Source voltage is out of the limit (180-242 VAC) and/or the environment temperature is also

close to the limit.

3. One or more phases of input power are missing.

RECOVERY:
1. Replace the controller.
2. Provide additional cooling to the enclosure.
3. Verify and correct the source voltage as required (between 180-242 VAC 3 phase).

Code A8_9 - SERVO AMPLIFIER ERROR / OVER SPEED.

The resolver signal received at the SAN controller indicates an over speed condition.

CAUSE:
1. The resolver cable or resolver has failed.

RECOVERY:
1. Check resolver using method in 7.2.3.
2. Replace resolver cable to spare cable.
3. Replace tool assembly.

Code A8_10 - SERVO AMPLIFIER ERROR / OVER LOAD (I SQUARE T)

The duty cycle of the press application is too severe for this size of tool, or for the parameters
currently setup.

RECOVERY:
1. Reduce duty cycle - Increase tool “downtime or off time” and/or increase Load Speed and

Slow Down Speed to reduce the amount of time running at high load/slow speed.

2. Increase the Speed Change Load or Crossover Distance at which Slow Down Speed shifts to

Load Speed.

If Speed Change Load is larger than 1

ST

Load, then 1

ST

Load will be used for

changing to Load Speed. Increase 1

ST

Load to be greater than Speed Change

Load.

3. If the problem remains, a larger tool assembly may be required for this application. Please

contact FEC.

Code A8_11 - SERVO AMPLIFIER ERROR / RESOLVER SIGNAL ERROR.

The resolver signal received is not correct.

RECOVERY:
1. Check the cable and look for loose connectors or visible damages to the cable.
2. Replace with known good tool.






Chapter 8: Troubleshooting