Input power supply connection – FEC DSP1500 (SAN3) User Manual

Page 38

Advertising
background image

PAGE 4-6

M

OT

O R

A

C 2 00 - 2 2 0 V

P

L C

T

/ D

SAN3-24S

1

:

F

G

2

:

W

3

:

V

4

:

U


enFORCE

Operation Manual

4.4 Input Power Supply Connection

Adequate circuit protection must be provided for the SAN unit input power.
Recommended conductor size should be a minimum of #16AWG.
Suggested color code (FEC standard): U – Red, V – White, W – Black, FG – Green.




Wiring Chart

SAN3-24S, 40S
4:U

3-Phase

3:V

180 ~ 242VAC

2:W

50/60Hz.

1:FG

SAN3-120S (Shown Below)
A5:U

B5:U 3-Phase

A4:V B4:V

180 ~ 242VAC

A3:W B3:W

50/60Hz.

A2:NC B2:NC
A1:FG B1:FG
*Connect wires to both the A side and B side.

Mating Connectors

SAN3-24S, 40S
Manufacture:

AMP

Housing Part No.:

1-178128-4

Contact Part No.:

1-175218-3 (Qty.-4)

SAN3-120S
Manufacture:

AMP

Housing Part No.:

1-917659-5

Contact Part No.:

1-917511-3 (Qty.-8)















Chapter 4: System Setup and Wiring

SAN3-120

5

4

3

2

1

B A

Advertising