PAGE 4-15

enFORCE

Operation Manual

ƒ

TIMING SIGNAL: [OUT DATA9] (Special Function)

This signal is active if Parameter 00, D-No. 0A (Option Output Signal) is set to a
number other than 0.
When activated, D-No. 30, 31, 32 and 33 of Parameters 1~32 (normally Rate 1 and
Rate 2 limits) will be used to set ON and OFF limits for the Timing Signal.

[30: Advance Direction ON Distance]

[31: Advance Direction OFF Distance]

[32: Return Direction ON Distance]

[33: Return Direction OFF Distance]

This may be useful when interfacing with other fixture processes or tooling (IE:
vacuum, clamps, etc.) or when other processes need to know when the press ram is
clear.
















ƒ

CYCLE OK: [OUT DATA10] (Special Function – Distance Control Methods)

This signal is active if Parameter 00, D-No. 0A (Option Output Signal) is set to a
number other than 0. When inactive this signal is the BANK 1 Input Echo signal.
This setting represents a distance (in millimeters) that the CYCLE OK signal will turn
on before reaching Standard Distance. The signal will turn off when Standard
Distance is reached. A setting of 1 to 9mm is possible.

Example: If Parameter 00, D-No. 0A is set to 6xxx. The CYCLE OK signal will

turn on 6mm before reaching Standard Distance.









Chapter 4: System Setup and Wiring

30

33

ON

OFF

31

OFF

ON

32

0mm

150mm

Standard Distance

ON

6 mm

Example #1

[30: 50.0mm]
[31: 120.0mm]
[32: 150.0mm]
[33: 100.0mm]

30

33

ON

OFF

150mm

Example #2

[30: 50.0mm]
[31: Max Distance]
[32: Max Distance]
[33: 100.0mm]

0mm