Chapter 5: Control Interfaces

5.10 Allen-Bradley Remote I/O Interface

The Allen Bradley (AB) Remote I/O communication interface allows slave connection to an AB
Remote I/O network. FEC has licensed (Lic. #

199906006

) the use of the AB Remote I/O interface

board (through HMS Fieldbus Systems). AB Remote I/O is a proprietary Fieldbus of Allen Bradley.
AB - RIO allows industrial devices to be controlled over a network architecture enabling device
connection at various locations in the field. This “Fieldbus” technology reduces hardwiring/cabling &
provides ease of installation. The network can have up to 240 nodes with valid rack addresses of
0-59. Maximum I/O data is 128 inputs & 128 outputs (Full Rack). 1/4, 1/2, 3/4 & Full rack
configuration is supported. (Default config. is 1/2 Rack 64In/64Out)

FEC integrates the AB Remote I/O board manufactured by HMS Fieldbus Systems into the Main
Unit modular I/O board. For further technical information on the AB Remote I/O interface see the
AnyBus -DT reference found at the end of this chapter or go to the HMS website. (

www.hms.se

)

Further AB Remote I/O information can be found through Allen Bradley’s website. (

www.ab.com

)


























Item Description

1 Application

Connector

2 Remote

I/O

Connector

3

Baud Rate / Station Number Setting Switch

4 Terminator

Switch

5 Status

LEDs

(3)

6 Watchdog

LED

Red - (flashing @ 2Hz) - ASIC and FLASH ROM check fault.
Green (flashing @ 2Hz) - module not initialized.
Green (flashing @ 1Hz) - module initialized and running OK.
Red (flashing @ 1Hz) - RAM check fault.
Red (flashing @ 4Hz) - DPRAM check fault.

5

3

2

1

6

4