enFORCE
DSP1500 Main Unit Hardware Manual
(Rev. 4.0)
PAGE 5 - 38
Chapter 5: Control Interfaces
Modbus Plus Specifications
Baud Rate
1M bits/sec.
Max. Nodes
32 (with repeaters - 64)
Max. Distance
2000m (with repeaters)
Max. Bus Cable Length
500m
Cable
RS-485 twisted pair (1-pair + Shield)
Communication Type
Master/Slave
Interface Specifications
Input data
16 words (256 bits)*
Output data
16 words (256 bits)*
Interface type
token bus interface
Operating Voltage
+5VDC / 200 ma
Data Width
8 bits
* Actual Input/Output data length is configurable using the DSP Software package.