FEC DSP1500 Main Unit User Manual
Page 113
Advertising

enFORCE
DSP1500 Main Unit Hardware Manual
PAGE 5 - 73
(Rev. 4.0)
Chapter 5: Control Interfaces
5.11.5 PLC Message Transfer Setup Example
This example procedure is written for using Rockwell Automation RXLogix5000 V15.02.00 and
Allen-Bradley Compact Logix L32E. Please contact your PLC manufacturer for specific setup
information.
Note: Allen-Bradley Control Logix configures up to 400 bytes per block with a maximum of 5
blocks of data for a total of 2000 bytes.
Configuration
1. Register the Main Unit to the network.
In the I/O configuration, right click on “Ethernet Port Local ENB” and select “New Module”.
Select “Generic Ethernet Module” from the “Module” list and click the OK button.