enFORCE

DSP1500 Main Unit Hardware Manual

PAGE 5 - 47

(Rev. 4.0)

Chapter 5: Control Interfaces

ON

8

5

4

2
3

7

6

1

ON

4

2
3

1

5.8.1 Component

Descriptions

Fieldbus Interface Connection


Pin 1

DA

Communication Line

Pin 2

DB

Communication Line

Pin 3

DG

Digital Ground

Pin 4

SHIELD

Connect cable shield

Pin 5

FG

Field Ground

Mating Connector: 5.08mm BU04/5 Hartmann or Equivalent


Wiring of the CC-Link network should be performed by using the cable listed in the CC-Link
Specifications. The three twisted conductors should be wired in series to each CC-Link device,
using a terminating resistor at the Master end and on the last Remote/Local device between the
DA & DB terminals.

Termination


Termination of the CC-Link requires a terminating resistor at each end of the fieldbus. Connect
120 ohm resistor between the DA & DB terminals if this is the last connection. (Remember that
the CC-Link master also needs to be terminated)


Station Number Setting (SW1)


Station Number switch sets the address in the CC-Link network. Max. number of stations is 64.
No two devices may share the same address. Switch setting format is Binary Coded Decimal
(BCD) Switch 1-4 is Least Significant Byte (LSB). Switch 5-8 is Most Significant Byte (MSB).

SW-1

SW-2

SW-3

SW-4

SW-5

SW-6

SW-7

SW-8

Station #

ON OFF OFF OFF OFF OFF OFF OFF

1

OFF ON OFF OFF OFF OFF OFF OFF

2

.

.

.

.

.

.

.

.

.

OFF OFF OFF OFF ON OFF OFF OFF

10

.

.

.

.

.

.

.

.

.

ON ON ON OFF OFF OFF ON OFF

47

.

.

.

.

.

.

.

.

.

OFF OFF ON OFF OFF ON ON OFF

64

This switch must be set before power is on and cannot be changed during operation.


Baud Rate Setting (SW2)

Baud

rate

SW-1

SW-2

SW-3

SW-4

156K OFF

OFF

OFF

OFF

625K ON

OFF

OFF

OFF

2.5M OFF

ON

OFF

OFF

5M ON

ON

OFF

OFF

10M OFF

OFF

ON

OFF

This setting MUST match the setting of the Master module. This switch must be set
before power is on and cannot be changed during operation.