Chapter 5: Control Interfaces

5.4.1 Component Descriptions


Fieldbus Interface Connectors

Bus IN

Pin No.

Signal

Description

Housing

PE Protective

Earth

Ground

1

DO1 Data

Output

2

DI1 Data

Input

3

GND Signal

Ground

4

NC -

5

NC -

6

/DO1 Inverted

Data

Output

7

/DI1 Inverted

Data

Input

8

NC -

(9 pin male D-sub)

9

NC -


Bus OUT

Pin No.

Signal

Description

Housing PE

Protective

Earth

Ground

1

DO2

Data

Output

2

DI2

Data

Input

3

GND

Signal

Ground

4

NC

-

5

GND

Signal

Ground

6

/DO2

Inverted

Data

Output

7

/DI2

Inverted

Data

Input

8

NC

-

(9 pin female D-sub)

9 RBST

*


*Always terminate RBST to ground if it is not the last module on the bus. If the RBST is not
connected to ground, the interface will automatically terminate the bus.

Baud Rate Switch


The module supports 2Mbit/s and 500Kbit/s operation. To select the
desired baud rate, just move the jumper cap to the corresponding
location.


Baud rate must be selected before power is on and cannot be changed during operation.


Status LEDs

No. LED Color

Description

1

CC/RC

Green

Cable connection is good & master not in reset

2

BA Green

Bus Active

3 RD Yellow

Remote Bus Disabled

4 TR Green

PCP - Communication active.
Hold Time = 500ms