1.3 Technical

Specifications

Table 1. CT-8000 Technical Specifications

TYPE Portable circuit-breaker analyzer

PHYSICAL SPECIFICATIONS

16”W x 11”H x 14”D (40.6 cm x 29.9 cm x 35.6 cm); Weight: 25 lbs (11.3 kg)

INPUT POWER

100 – 120 Vac or 200 – 240 Vac (selectable), 50/60Hz

DRY-CONTACT INPUT 3 or 6 dry-input channels (depending on model). Each channel detects main and

insertion-resistor contacts

TIMING WINDOWS 1-second, 10-seconds, or 20-seconds

TIMING RESOLUTIONS

±50 micro-seconds @ 1-second duration,

±0.5 milliseconds @ 10-second duration,
±1.00 milliseconds @ 20-second duration

TIMING ACCURACY 0.05% of reading ±50 micro-seconds @ 1-second duration

CONTACT DETECTION RANGE Closed: less than 20 ohms; Open: greater than 5,000 ohms

RESISTOR DETECTION RANGE 50 – 5,000 Ohms

CT CURRENT SENSOR One, non-contact, 0 – 100 Amperes

TRIGGER INPUT VOLTAGE Open/Close: 30 – 300V, DC or peak AC

VOLTAGE SENSING INPUT

RANGE

V1: analog input; 0 – 255V DC or peak AC; Sensitivity ±1V
V2: voltage presence/absence detector input; 30 – 300V DC or peak AC

BREAKER OPERATIONS

Initiate Open, Close, Open– Close, Close – Open, Open – Close – Open

BREAKER INITIATE CAPACITY 25A, 250Vac/dc max (100A Inrush)

INITIATE CURRENT READING

RANGE

One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz

TRAVEL TRANSDUCER INPUTS 3 digital travel transducer channels; Linear range, 0.0 – 30.0 in (±0.01 in); Rotary

range: 0 – 360 degrees (±0.36 degrees)

CONTACT TRAVEL POINT

DIFFERENCE

Measures “slow-close” contact-point distances; results can be printed

DYNAMIC/STATIC RESISTANCE

RANGE

0.1 – 1,999 micro-ohms; Accuracy: ±2% of reading, ±5 micro-ohms

RESISTANCE TEST CURRENT 200 Amperes typical

RESISTOR TYPE TRANSDUCER

INPUT

200 Ohms – 10K Ohms

DISPLAY Back-lit LCD Screen (20 characters by 4 lines); viewable in bright sunlight and low-light

levels

PRINTER Built-in 4.5-inch wide thermal printer can print both graphic contact travel waveforms

and tabulated test results

INTERNAL TEST RECORD

STORAGE

Stores up to 150 test records and 99 test plans

COMPUTER INTERFACES One RS-232C port, One USB port

PC SOFTWARE Windows

®

XP/Vista-based Breaker-Analysis software is included with purchase price

SAFETY Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards

ENVIRONMENT Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)

HUMIDITY (MAX)

90% RH @ 40˚ C (104˚ F) non-condensing

ALTITUDE (MAX) 2000m (6562 ft) to fully safety specifications

OPTIONS

Transportation case (available for the CT-8000 and the travel transducers)

WARRANTY One year on parts and labor

NOTE

The above specifications are valid at nominal operating voltage and at a
temperature of 25

°C (77°F). Specifications may change without prior notice.