Vanguard CT-8000 User Manual

Page 77

Advertising
background image

REV 2 CT-8000 USER’S MANUAL

72

3.4

Performing a Static Resistance Test

The CT-8000 can also be used as a 200 Ampere micro-ohmmeter. A typical connection for this
application is shown in Figure 11. Follow the steps below to perform a static resistance test:

a. Start from the “START-UP” menu:

Press the

[1]

key (RUN TEST).

b. The following screen will be displayed:

Press the

[2]

key (STATIC RES TEST).

c. The following screen will be displayed:

Press the

[ENTER]

key.

d. The following screen will be displayed momentarily:

Once the test is complete, the results will be displayed as shown below:

Press any key to return to the “START-UP” menu. You can print the test results using the
instructions in section 3.3.5. A typical static resistance report is shown in Figure 30.

TEST COMPLETE

RES = 291.6 u-Ohms
CUR = 205.9 A

CABLES ENERGIZED!



STATIC RES TEST

CONNECT DCR CABLES

THEN

“ENTER” TO BEGIN

1. TIME BREAKER

2. STATIC RES TEST

3. DYNAMIC RES TEST

1. RUN TEST 03/10/10

2. GET RSLT 09:04:05

3. SETUP

4. DIAGNOSTICS

Advertising