3.7

Working With Test Plans

The CT-8000 comes with the Vanguard Circuit Breaker Analysis PC Software that can be used to
create circuit breaker test plans. The test plans can then be transferred to the CT-8000. The CT-
8000 can store up to 99 circuit breaker test plans in its Flash EEPROM.

A circuit breaker test plan contains breaker maximum/minimum parameters and can be used to
quickly test a breaker. A typical list of operating parameters in a test plan includes the
following:

• Max/Min Contact/Resistor Trip Time

• Max/Min Contact/Resistor CLOSE time

• Max Contact Spread Time

• Max Resistor Contact Spread Time

• Max/Min Contact CLOSE-OPEN Time

• Max/Min Contact OPEN-CLOSE Time

• Max/Min Resistor CLOSE-OPEN Time

• Max/Min Resistor OPEN-CLOSE Time

• Max/Min Breaker Stroke

• Max/Min Breaker Trip Velocity

• Max/Min Breaker CLOSE Velocity

• Max/Min Breaker Over-Travel

• Max/Min Breaker Bounce-Back

• Trip Velocity Analysis Calculation Points

• CLOSE Velocity Analysis Calculation Points

If a timing test is executed with a breaker test plan, the timing report will display a Pass/Fail
indicator for each of the parameters tested. The Pass/Fail status is determined by comparing
the values in the test plan to the timing test results.

3.7.1. Recalling a Breaker Test Plan for Use

Use the steps below to recall a breaker test plan to use for a timing test:

a. Start from the “START-UP” menu:

Press the

[3]

key (SETUP).

1. RUN TEST 03/10/10

2. GET RSLT 09:04:05

3. SETUP

4. DIAGNOSTICS