Table 2. Functional Descriptions of CT-8000 Controls and Indicators

Item

Number

Panel Markings

Functional Description

1, 6, 7

D1, D2, D3

TRANSDUCER

INPUT

16-pin connectors. Digital travel transducer input channels.

2

0-300V

V1

3-pin connector. V1 voltage input channel is dedicated to monitoring circuit
breaker DC power supply or coil voltages. Voltage sensing range is from 0-255
volts, dc or peak ac.

3

0-300V

V2

3-pin connector. V2 voltage input channel is dedicated to detecting voltage
on/off status (present or absent) of an A/B switch. Voltage input ranges from
0-300 volts, dc or peak ac.

4

0-300V

TRIGGER

3-pin connector. Triggers voltage input for external trigger application. Voltage
levels ranging from 30 to 300 V, dc or peak ac.

5

CT

5-pin connector. AC current input channel. Detects CB load current for Quick-
Shot application.

8, 11

5VDC, 200A

200A Micro-Ohm Meter current output terminals.

9, 10

Micro-Ohm Meter sense inputs.

12

GROUND

Safety ground terminal.

13

100-120 Vac, 8A,

50-60Hz

Power plug and power switch. Built-in 12 Ampere circuit breaker.

14

R1

5-pin connector. Resistor type transducer input.

15

INITIATE

4-pin connector used for the switching circuit for operating the circuit breaker
under test.

16

OPEN

250V,

5A FAST-BLOW

Open circuit fuse: 5 Ampere, 250V, Fast-Blow.

17

CLOSE

250V,

5A FAST-BLOW

Close circuit fuse: 5 Ampere, 250V, Fast-Blow.

18

Built-in 4.5-inch wide thermal printer.

19

“PUSH” TO ARM

Spring-loaded pushbutton switch. Press and hold to complete the Trip or Close
circuits for breaker tests.

20

Rugged alpha-numeric membrane keypad.

21

Back-lit LCD screen (20 characters by 4 lines); viewable in bright sunlight and
low-light levels.

22

RS-232C

RS-232C serial computer interface port.

23

USB

USB computer interface port.

24, 25, 26

CONTACT INPUT

(C1-C6)

Female connectors for the contact channels.