App index alarm dsplay, Alarm output relay operaton – Yokogawa Button Operated MV2000 User Manual

Page 16

Advertising
background image

1-7

IM MV1000-01E

Feature Overv

ew

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Alarm dsplay

Alarm conditions are indicated in operation windows (trend, digital, bar graph, overview,
etc.) and by icons in the status display section. The alarm summary displays detailed
alarm information.

• Hold/Nonhold of Indcaton

When alarm conditions cease, their indicators can be set to either:
• Stop as soon as the alarm condition ceases (Nonhold).
• Continue until the execution of an alarm output release (AlarmACK) operation (Hold).
The default setting is Nonhold.

For configuration instructions, see Section 3.5.

• Alarm Hde Functon

If this function is enabled, the MV will not display alarm condition information or record

it in the alarm summary. However, the MV will output alarm information to a relay (/A
options) or internal switch. You can set this function for each channel and alarm.

For configuration instructions, see Section 3.6.

Alarm Output Relay Operaton

The MV can generate a contact signal from an alarm output relay (/A options) when an
alarm occurs. The alarm output relay operation can be changed.

For configuration instructions, see Section 3.5.

Alarm

Alarm output relay

(reflash ON)

Alarm output relay

(reflash OFF)

Channel 1

Channel 3

Channel 2

Approx.

500 ms

Approx.

500 ms

Energize or De-energize

Non-Hold

Hold

AND/OR

Alarm

Channel 1

AND

Channel 2

OR

Alarm output relay

or

Internal switch

NO

Energize

De-energize

C NC

NO C NC

NO C NC

NO C NC

NO C NC

NO C NC

When power is shut down

NO: Normally Opened

C: Common

NC: Normally Closed

Normal operation

When alarm is occurring

Alarm

Alarm occurrence

Alarm occurrence

Alarm release

Alarm release

Alarm

output

relay

Alarm
Alarm

output

relay

AlarmACK

AlarmACK

or

or

or

Activated

Activated

Deactivated

Deactivated

Activated

Deactivated

AlarmACK

Activated

Deactivated

Activated

Deactivated

AlarmACK

Activated

Deactivated

AlarmACK

Activated

Deactivated

Reflash

(You can set the alarm output relay and internal

switch. For details on the internal switch, see the

next page.)

(when a relay is set to “OR” logic)

Relay is activated

at the next scan

interval

Relay is activated

at the next alarm

occurrence

Normal

Reset

Relay

Action on

AlarmACK

1.3 Alarms

Advertising
This manual is related to the following products: