1-28

IM MV1000-01E

Dsplay and Event Data Recordng Methods

For configuration instructions, see section 4.1. For operating instructions, see section
4.4.

• Types of Recorded Data

You can choose to record display data only, event and display data, or event data

only.

Choosng What Type of Data to Record

Record the type of data that meets your needs. Use the following examples for

reference.

Example 1 To record continuous waveform data only, just like conventional chart

recorders:

Record display data.

Example 2 To record waveform data continuously and record more detailed data

before and after an alarm event:

Record display data continuously and use an alarm to trigger the
recording of event data.

Example 3 To continuously record data that is as detailed as possible:

Set the sampling interval and record event data.

Example 4 If there is no need to record data continuously but you want to record

data when an alarm occurs:

Use an alarm to trigger the recording of event data.

• Internal Memory

Measured data is partitioned and saved to files at set intervals. If the internal memory

is full or if the number of display data files and event data files exceeds 400, files are
overwritten from the oldest file.

• Dsplay Data Recordng Condtons

Item

Descrpton

Channel type

You can set the channel type to measurement, computation, or

(only with the MV2000) external input.

Sampling interval

Determined by setting the Trend/Storage interval. Choices are

available in the range of 5 s to 10 h. You cannot choose an

interval that is faster than the scan interval.

File generation

Files are generated at the set file save interval.

Time

File

File

File

Adding data

Files are also generated in these cases:
• When you generate a file manually.
• When there is a memory stop.
• When a file is generated using the event action function.
• After recovering from a power failure.

Memory start/stop

Pressing START/STOP starts recording (memory start). Pressing

START/STOP again stops recording (memory stop).

1.5 Data Storage Functons