Other tme settngs – Yokogawa Button Operated MV2000 User Manual

Page 210

Advertising
background image

9-2

IM MV1000-01E

Other Tme Settngs

Set the time zone of the region where the MV will be used, the time correction operation
during memory sampling, and the date format. Be sure to set the time zone if you are
using Ethernet network functions.

Dsplay

Press

MENU and then select Menu tab > Basc settng mode > Menu tab > Tme

settngs.

Settngs

• Tme settngs > Tme zone (HHMM)

Set the time zone of the region where the MV will be used in terms of the time

difference from GMT. Specify a value in the range of –1300 to 1300 (where the first
two digits denote the hour and the last two digits denote the minute). A negative value
indicates that the local time is behind GMT.

Example: The standard time in Japan is ahead of GMT by 9 hours. In this case, enter

900.

• Tme settngs > Tme devaton lmt

Time deviation limit

Current time

Specified time

When the time deviation between the time on the MV and the specified time is within

±(the value specified here), the time on the MV is gradually corrected. Otherwise, the
time is corrected immediately.

Settng

Descrpton

10s to 5min

The time deviation limit.

Off

Disables gradual time correction.

Example: If Time deviation limit is set to 10s and the time on the MV is 10 hours 21

minutes 15 seconds, the time is gradually corrected if the specified time
is between 10 hours 21 minutes 5 seconds and 10 hours 21 minutes 25
seconds.

9.1 Settng the Date and Tme

Advertising
This manual is related to the following products: