Yokogawa Button Operated MV2000 User Manual

Page 56

Advertising
background image

1-47

IM MV1000-01E

Feature Overv

ew

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Specal Data Handlng Cases and Exceptons

This section explains special data handling cases and exceptions for TLOG computation,
CLOG computation, and reports.

• Power Falure Data Handlng (for TLOG and reports)

If a power failure occurs when the report function is enabled or in the middle of a

TLOG operation, the report and TLOG operations resume when the MV recovers from
the power failure. The operation executed after recovery varies depending on whether
the MV recovers from the power failure before or after the report or TLOG data
production time.

Tme of Recovery

Operaton

After the data

production time

The report or TLOG data is produced immediately after the MV

recovers. The measured data up to the time of the power failure

is used. When the next report or TLOG is produced, the data after

recovery from the power failure is used.

Before the data

production time

After the MV recovers, the report or TLOG is produced at the data

production time. The measured data is used with the data for the

power failure period left out.

• Handlng of Abnormal Data (TLOG, CLOG, and reports)

If an error occurs in channel or other data, the abnormal data is discarded, and the

computation continues. If all of the data is abnormal, an error message is produced.

The following result in abnormal data:
• When channels are set to Skip or Off.
• When an error value is returned as a measured result on a measurement channel

(A/D converter failure, etc.).

• When a measurement channel is in a burnout condition
• When an error value is returned as the computed result on a computation channel.
• When an external input channel is Off or when data is not being received from it (in

cases such as when communication is prohibited).

• How Overflow Data Is Handled

* Overflow data refers to range-out values on measurement, computation, and external input

channels.

For TLOG, CLOG, and reports

Channel overflow data is handled in the following ways:

Operaton

Descrpton

Average, Sum

You can choose from three methods of handling the data: ERROR,

SKIP, and LIMIT.
ERROR: Treats the data as a computation error.
SKIP:

Discards the overflow data and continues the computation.

LIMIT:

Replaces the data with the limit value and continues the

computation.
The limit value is the span upper or lower limit, or the scale

upper or lower limit of the channel.

Maximum, minimum,

maximum-minimum

You can choose one of two methods of handling the data: OVER, or

SKIP.
OVER:

Performs the computation using the overflow data.

SKIP:

Discards the overflow data and continues the computation.

For Multplcaton, and Relatonal Computatons EQ and NE

Operaton Type

Calculated Values

Computed Result

Multiplication

0*(+Over)

0

0*(-Over)

0

(+Over)*0

0

(-Over)*0

0

.EQ.

(+Over).EQ.(+Over)

0

(-Over).EQ.(-Over)

0

.NE.

(+Over).NE.(+Over)

1

(-Over).NE.(-Over)

1

1.9 Computaton and Report Functons (/M1 and /PM1 optons)

Advertising
This manual is related to the following products: