11 other functions, 11 other functions -50, 11 other functons – Yokogawa Button Operated MV2000 User Manual

Page 59: Tme related functons

Advertising
background image

1-50

IM MV1000-01E

1.11 Other Functons

Tme Related Functons

• Tme Correcton

The MV internal clock can be changed in the following ways.

Method

Descrpton

Key operation

Use to set the MV to a specified time.

Event action function Sets the MV internal clock to the closest hour.
SNTP client function

Sets the MV internal clock to the time retrieved from an SNTP server.

Tme Correcton Operaton

The time correction operation varies depending on whether or not memory sampling is

in progress.

For configuration instructions, see section 9.1.

Status

Operaton

No memory sampling The MV internal clock is changed immediately.
Memory sampling

The MV internal clock is gradually corrected. While the time is being

gradually adjusted, the date/time in the status display section is

displayed in yellow.

Gradual Correcton of the Internal Clock

If the time deviation between the time of the MV internal clock and the correct time (the

specified time) is within a specified value, the MV clock is adjusted gradually at 40 ms
for each second. Otherwise, the clock is corrected immediately. The maximum value
of time deviation (referred to as tm in the figure below) can be selected from within the
range of 10 s to 5 min.

Time specified manually or retrieved

from an SNTP server

Range in which the time is

gradually adjusted

Nearest hour

Time deviation

Time when a remote control

signal is applied (Time on the MV)

tm

tm

Range in which the time is

gradually adjusted

Time on the MV

Time deviation

tm

tm

Example: When changing the time to 12 hours 55 minutes 35 seconds when the time

on the internal clock is 12 hours 55 minutes 32 seconds

The time deviation of 3 seconds is adjusted by 40 ms per second. The internal

clock will be fully synchronized to the specified time after 75 seconds.

• Date Format

You can select from the following ways of displaying the year, month, and day:

2008/01/23, 01/23/2008, 23/01/2008, and 23.01.2008.

For configuration instructions, see section 9.1.

• Tme Zone

You can set the time difference between the location where the MV is used and GMT.

For configuration instructions, see section 9.1.

• Daylght Savng Tme (DST)

If the MV is used in a region that has DST, the time is switched automatically between

DST and standard time at two user-specified times. For configuration instructions, see