2.2 Sgnal Input Termnal Wrng

Wrng to the Sgnal Input Termnals

WAR

WARNING

• To prevent electric shock, make sure that the power source is turned OFF.

CAUTION

• Exposing the input and output signal cables connected to the MV to high tension

may damage the cables and the MV terminals. Do not stretch the cables to their
limit, and make sure that the terminals are not being pulled on.

• To prevent fire, only use signal cables with a temperature rating of 70°C or

above.

• Do not run a current through any of the input terminals that exceeds the voltages

below. Doing so may damage the MV.

• Maximum input voltage: ±60 VDC
• Maximum common mode voltage: ±60 VDC (under measurement category II

conditions)

• The MV is an installation category II product.

Wrng Precautons

Take the following precautions when wiring the input signal cables:
When usng a screw termnal, we recommend that you use a crmp-on lug wth an
nsulaton sleeve (desgned for 4-mm screws).

Crimp-on lug (designed for 4-mm screws) with an insulation sleeve

When using a clamp terminal, we recommend that you use the following kind of cable:
• Conductive cross-sectional area: 0.08 mm

2

to 1.5 mm

2

(AWG28 to 16)

• Stripped section: Approx. 7 mm

Take measures to prevent nose from enterng the measurement crcut.
• Move the measurement circuit away from the power cable (power circuit) and ground

circuit.

• Ideally, the object being measured should not generate noise. However, if this is

unavoidable, isolate the measurement circuit from the object. Also, ground the object
being measured.

• Shielded wires minimize the noise caused by electrostatic induction. Connect a shield

to the ground terminal of the MV as necessary (make sure you are not grounding at
two points).

• To minimize noise caused by electromagnetic induction, twist the measurement circuit

wires at short, equal intervals.

• Make sure to ground the protective ground terminal through minimum resistance (less

than 100 Ω).

When usng nternal reference juncton compensaton on a thermocouple nput,
take measures to stablze the temperature at the nput termnal.
• Always use the terminal cover.
• Do not use thick wires which may cause large heat dissipation (we recommend a

cross-sectional area of 0.5 mm

2

or less).

• Make sure that the ambient temperature remains reasonably stable. Large

temperature fluctuations can occur if a nearby fan turns ON or OFF.