Yokogawa Button Operated MV2000 User Manual

Page 88

Advertising
background image

3-8

IM MV1000-01E

• Basc settngs > Rate of change

• Decrease

Set the interval for the rate-of-change calculation of the low limit on rate-of-change

alarm by the number of sampled data points (1 to 32). The actual interval is
obtained by multiplying the value specified here by the scan interval.

• Increase

Set the interval for the rate-of-change calculation of the high limit on rate-of-change

alarm in the same manner as the interval for the low limit on rate-of-change alarm.

• Basc settngs > Indcator

You can choose to make the alarm displays behave in the following ways.

Settng

Descrpton

Nonhold

Stop when the alarm condition is released (return to normal condition).

Hold

Continue until an alarm output release (AlarmACK) operation is performed.

• Swtch, Relay

• Internal Swtch > AND

Select the internal switches you want to set to AND logic. Select how many

switches after and including the first switch will be set to AND logic. All other
switches will be set to OR logic.

• Relay > AND

Select the relays you want to set to AND logic. Select how many relays after and

including the first alarm output relay will be set to AND logic. All relays after the
selected last relay will be set to OR logic. Available settings are None, I01 (I01
only), I01-I02 (I01 and I02), I01-I03 (I01 to I03), etc. Only alarm output relays that
are installed are valid.

Note

When reflash is turned ON, the operation of the first three output relays is fixed to OR logic.
Specifying AND produces no effect.

• Relay > Acton

Select whether to energize or de-energize the alarm output relay when an alarm

occurs. This setting applies to all alarm output relays.

• Relay > Hold

You can choose to make the alarm output relays behave in the following ways. This

setting applies to all relays.

Settng

Descrpton

Nonhold

Stop when the alarm condition is released (return to normal condition).

Hold

Stay ON until an alarm output release (AlarmACK) operation is performed

Note

When reflash is turned ON, the operation of the first three output relays is fixed to Nonhold.
Specifying Hold produces no effect.

• Relay > Relay Acton on ACK

You can select the relay output status that is enabled after the AlarmACK operation

from the following two settings.

Settng

Descrpton

Normal

The relay output is deactivated when the AlarmACK operation is executed. If the

condition for activating the alarm output relay is met in the next scan interval, the

relay output is activated.
The operation only applies when the alarm output relay is set to Hold.

Reset

The relay output is deactivated when the AlarmACK operation is executed. If a

new condition for activating the alarm output relay is met, the relay is activated.

3.5 Settng the Auxlary Alarm Functon

Advertising
This manual is related to the following products: