IM MV1000-01E

Installat

on and W

rng

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Screw Termnal Wrng

+

+

DC voltage input

TC input

DC voltage input/DI (ON/OFF) input

RTD input

DC current input

DC current input

Shunt resistor
Example: For 4 to 20 mA input, use a

shunt resistor of 250 Ω

+

+

+

A

B

b

Lead wire resistance per wire of
10 Ω or less. Make the resistance
of the three wires equal.

A

b

B

Compensating leadwire

±0.1%.

Clamp Termnal Wrng

Remove the terminal block

Hold both ends of the terminal

block and pull straight.

Input signal wire

First, loosen the screw at the front using

a flat-blade screwdriver. Insert the input

signal wire into the slit on the left side of

the terminal block, and fasten the screw

at the front.

Recommended wire size

0.08 to 1.5 mm

2

(AWG28 to 16)

Recommended length

of stripped wire:

7 mm

Connect the wires

Flat-blade

screwdriver

Hold both ends of the terminal

block, align it with the connector,

and then push it in.

Connect the terminal block

Note

RTD input terminals A and B are isolated on each channel. Terminal b is shorted internally
across all channels. On models with the /N1 option (Cu10, Cu25 RTD input/3-wire isolated
RTD) or the /N2 option (3-wire isolated RTD), terminal b is also isolated on each channel.

2.2 Sgnal Input Termnal Wrng