Clog computaton – Yokogawa Button Operated MV2000 User Manual

Page 230

Advertising
background image

10-10

IM MV1000-01E

CLOG Computaton

Only data from measurement, computation, and external input channels can be used in a
CLOG computation. Up to 30 channels can be written inside the parentheses.
In the explanation below, an operator or function cannot be placed inside the
parentheses. Also, an expression can contain only one CLOG function.

CLOG.SUM( )

Sum value
(Syntax) CLOG.SUM(e1.e2.e4-e6)
(Condition) Determines the sum of the data of channels e1, e2, e4, e5, and e6 that

are measured at the same time.

CLOG.MAX( )

Maximum value
(Syntax) CLOG.MAX(e1.e2.e4-e6)
(Condition) Returns the maximum measured data value at a given point in time

from channels e1, e2, e4, e5, and e6.

CLOG.MIN( )

Minimum value
(Syntax) CLOG.MIN(e1.e2.e5.e7)
(Condition) Returns the minimum measured data value at a given point in time from

channels e1, e2, e5, and e7.

CLOG.AVE( )

Average value
(Syntax) CLOG.AVE(e1-e6)
(Condition) Returns the average of the measured data values of channels e1 to e6

at a given point in time.

CLOG.P-P( )

Maximum – minimum value
(Syntax) CLOG.P-P(e1.e2.e5.e7)
(Condition) Returns the difference between the maximum and minimum data values

measured at a given point in time from channels e1, e2, e5, and e7.

Expresson Example

CLOG.MAX(001.002.I04-I06)+K01*SQR(002)

Examples of Invald Expressons

CLOG.AVE(001.003.005)+CLOG.AVE(002.004.006)
Reason: CLOG appears twice in one expression.

CLOG.AVE(001.ABS(001))
Reason: A function is used inside the parentheses.

10.2 Wrtng Expressons

Advertising
This manual is related to the following products: