Report Channels

There are sixty report channels, from R01 to R60. You can assign channels for measuring objects

being computed or computation channels and the type of computing on a report-channel basis.

When making a report of computed data, let computing start before letting the report making start.

Types of Computing

Setting Parameter

Data Item for Computing

INST

Instantaneous value at the time of making report

AVE

Average, maximum and minimum over the computing period

SUM

Sum and cumulative sum over the computing period

Sum and Cumulative Sum

Sum:

The total sum over an hour for hourly reports, the sum over a day for daily

reports or the sum over a month for monthly reports. The DA resets this value

each time it makes any of these reports.

Cumulative sum:The total sum up to the preset time to make a report in the case of hourly

reports or the sum up to a preset time of the day to make a report in the case of

daily reports. The DA resets this value at each preset time or at each preset

time of the day for report making. The DA does not perform cumulative

summation for monthly reports.

As an example, the following illustrates the process of summation and cumulative summation for

hourly reports. The example shows the case where the preset time to make a report is 8:00.

9:00

11:00

Results of computing

Time to make an hourly report

Time

7:00

10:00

8:00

8:00

9:00

10:00

Cumulative summation

Summation

Preset time to make report

Unit of Summation (SUM UNIT)

Such input data items as the flowrate that have a unit in /sec, /min, /hour or /day, when simply

summed, give results of computing different from their actual values. This occurs because the unit

of such a data item differs from that of the measurement interval. In that case, you can take the

output after having converted the unit of summation so it matches that of the input data item applied.

Unit of Input (Preset Unit)

Conversion Formula

INTVL (no conversion)

Σ

(measured data values)

/sec

Σ

(measured data values)

×

measurement interval

/min

Σ

(measured data values)

×

measurement interval/60

/hour

Σ

(measured data values)

×

measurement interval/3600

/day