Dr start/stop the report, Rs executes a system reconstruction, Rc executes the initializing of set values – Yokogawa DA100 User Manual

Page 63: Ds transfers the setting mode

Advertising
background image

IM DA100-11E

6-11

Commands

6

• If initial balancing is executed, number-of-

channels worth of data are returned in the
following format.
S1 S2 CCC DDCrLf

S1:

Data status 1
N: Normal
S: SKIP

S2:

Data status 2
Space: Data in the middle
E: Data at the end

CCC: Channel number
DD: Result of the initial balancing

OK: Initial balancing succeeded
NG: Initial balancing failed
DF: Default values set
_: Skip module

DR

Start/stop the report

Mode

Operation mode

Setting

DRp1<terminator>

p1 Start/stop the report

0: Start the report
1: Stop the report

Example

Start the report.

DR0

Comments

• Effective only on instruments with the optional

report function.

• Measurement range, date, time cannot be

changed during a report. Copy using the range
copy ON also cannot be executed during a
report.

• All report data up to that point are cleared when

a report is started.

• This setting is effective when one of hourly,

daily and monthly reports is ON.

RS

Executes a system reconstruction.

Mode

Operation mode

Setting

RSp1<terminator>

p1

0, Reconstruct the system.

Example

Reconstruct the system.

RS0

Comments

• Reconstruct the system. Execute this command

if a subunit or a module is newly added or a
module in a slot is replaced.

• Since it takes an indefinite time to execute the

RS command, return an ACK after processing.
On the controller side, execute the following
processing after receiving the ACK after
transmitting the RS command. The ACK status
format is as shown below.

E0Cr+Lf: The received command has been

normally processed.

E1Cr+Lf: There is an error in the received

command.

• After executing the command, the clock is

initialized to 96/01/01 00:00:00.

RC

Executes the initializing of set values.

Mode

Operation mode

Setting

RCp1<terminator>

p1

0, Initialize the set values.

Example

Initialize the operation mode parameters
(measuring range, unit, alarm, date & time, and
moving average).

RC0

Comments

• Since it takes an indefinite time to execute the

RC command, return an ACK after processing.
On the controller side, execute the following
processing after receiving the ACK after
transmitting the RC command. The ACK status
format is as shown below.
E0Cr+Lf: The received command has been

normally processed.

E1Cr+Lf: There is an error in the received

command.

• After executing the command, the clock is

initialized to 96/01/01 00:00:00.

DS

Transfers the setting mode.

Mode

All modes

Setting

DSp1<terminator>

p1

0 Transferred to operation mode.
1 Transferred to setup mode.
2 Transferred to A/D calibration mode.

Example

Transfer the DA100 mode to the setup mode.

DS1

Comments

• Since it takes an indefinite time to execute the

DS command, return an ACK after processing.
On the controller side, execute the following
processing after receiving the ACK after
transmitting the DS command. The ACK status
format is as shown below.
E0Cr+Lf: The received command has been

normally processed.

E1Cr+Lf: There is an error in the received

command.

• After executing the command, the clock is

initialized to 96/01/01 00:00:00.

VD

Turn ON/OFF the relays specified by the
VS command.

Mode

Operation mode

Setting

VDp1, p2, p3<terminator>

p1 First relay number of the module (I01 to

560, S01 to S60)

p2 Setting procedures

SET

Set the relay corresponding to the
“1” bit specified by p3 to ON, and
the relay corresponding to the “0”
bit to OFF.

ON

Set the relay corresponding to the
“1” bit specified by p3 to ON.

OFF

Set the relay corresponding to the
“1” bit specified by p3 to OFF.

p3 Setting pattern for one module

Four four-bit values (total of 16 bits), each
displayed in hexadecimal notation.

1

2

16

0 0 0 0 0 0 1 1 1 0 0 0 1 1 1 1

F

8

3

0

Bit No.

3

4

5

6

7

8

9

10

11

12

13

14

15

First relay

The value of p3

Last relay

Setting pattern

Example

Turn ON relay 11 to 15 and maintain 16 to 20 at
the current condition of sub unit 1.
VD111, ON, 001F

Comments

• Because the settings are done on a module basis,

set p1 to the first relay number of the module.

• If p2 is set to ON, the relays with the setting

parameters of 1 are turned ON, and those of 0
maintain the current condition.

6.2 Control Execution Command

Advertising