8 xj selection of reference junction compensation, Xg sets computation error handling, Xe establishes content of the setup mode setting – Yokogawa DA100 User Manual

Page 60

Advertising
background image

IM DA100-11E

6-8

XJ

Selection of reference junction
compensation

Mode

Setup mode

Setting

XJp1, p2, p3<terminator>

p1

Channel number (001 to 560)

p2

Selection of reference junction
compensation value

INT

Internal compensation circuit

EXT External junction compensation

p3

External reference junction compensation
value
(-20000 to 20000)

Example

Set channel 01 of subunit 0 to external junction
compensation at a compensation value of 1000

µ

V.

XJ001, EXT, 1000

Comments

• For p2 = INT, parameter p3 is ineffective.
• Unit of p3 is

µ

V.

XG

Sets computation error handling.

Mode

Operation mode

Setting

XGp1, p2, p3, p4, p5<terminator>

p1 Computation error handling (+OVER/-

OVER)

p2 Scale unit for TLOG computation (OFF, /

SEC, /MIN, /HOUR)

p3 Handling of abnormal data in a channel for

TLOG computation

ERROR: Handled as computation error.
SKIP:

Abnormal data are skipped
(ignored) and computations are
executed.

p4 Handling of overflow data in a channel for

TLOG computation

ERROR: Handled as computation error.
SKIP:

Abnormal data are skipped
(ignored) and computations are
executed.

LIMIT: If linear scaling has been set, its

upper- and lower-limit values
are computed. If it has not been
set, the upper- and lower-limit
values in the measurement
range are computed.

p5

handling of data for TLOG.PSUM(only

for PULSE input module)

OVER A result of the computational

expression TLOG.PSUM
(XXX) exceeding 99999999 as
an overflow

ROTATE

A result of the computational

expression TLOG.PSUM
(XXXX) exceeding 99999999
to continue computing with the
value following 99999999
reset to 0.

.

Example

Compute computation error as +OVER and TLOG
computation scale value as off, and ignore
abnormal data in a channel and overflow data in a
channel for computation and a result of the
computational expression TLOG.PSUM (XXX)
exceeding 99999999 as an overflow.

XG+OVER, OFF, SKIP, SKIP, OVER

Comments

• This command only works with the optional

computation function or if a pulse module is
installed.

• p2 is effective for the totalization of flow

signals, which are expressed in engineering
units /s, /min, /h.
If p2 is set according to the input unit, the
measurement data are computed based on that
unit at the specified measurement intervals. For
example, set the measurement interval to 2s,
the input value to 100 m3/min, and p2 to /MIN.
By doing this, because 2s/60s is multiplied for
each measurement interval, then after 1 minute,
approximate actual input values are obtained.

VS

Selects the relay that can be turned ON/
OFF externally.

Mode

Setup mode

Setting

VSp1, p2<terminator>

p1 Unit number

I

DA100 main unit

S

Internal switch

0 to 5

Sub units 0 to 5

p2 Number of relay that can be turned ON/Off

externally

NONE

No relay

01 to 10

Relay numbers 01 to 10

01 to 20

Relay numbers 01 to 20

01 to 30

Relay numbers 01 to 30

01 to 40

Relay numbers 01 to 40

01 to 50

Relay numbers 01 to 50

01 to 60

Relay number 01 to 60

Example

Specify the relays from the first of slot 0 to the
10th of slot 2 in sub unit 0 to those which can be
turned ON/OFF externally.
VS0, 01-30

Comments

• p2 is set with number of the first relay (fixed to

01), and that of the last relay.

• The relays specified here can only be turned

ON/OFF by using the VD command.

• Configurations such as alarm reflash, AND/OR,

and hold are ineffective for the relays specified
here.

XE

Establishes content of the setup mode
setting.

Mode

Setup mode

Setting

XEp1<terminator>

p1

Selection of establishment or destruction

STORE

Establishment

ABORT

Destruction

Example

Store a parameter set in the setup mode in
NVRAM.

XESTORE

Comments

• A parameter set in the setup mode becomes

ineffective in its setting if the mode is changed
without STORE. After setting all parameters
in the setup mode, be sure to store the set data
in the internal memory using the XE command.
In addition, after normal processing with the
XE command, the mode is transferred to the
operation mode.

• Since execution of the XE command takes an

indefinite time, return an ACK after the
processing is completed. On the controller side,
execute the next processing after receiving an
ACK after transmitting the XE command. The
ACK status format is as follows:

6.1 Setting Command