Sl sets an event/action, So sets the computational expression, Sk sets the computational constants – Yokogawa DA100 User Manual

Page 57

Advertising
background image

IM DA100-11E

6-5

Commands

6

6.1 Setting Command

SL

Sets an event/action.

Mode

Operation mode

Release of event/action setting

Setting

SLp1, p2<terminator>

p1 event/action box number (01 to 30)
p2 NONE

Event action setting by an alarm

Setting

SLp1, p2, p3, p4, p5<terminator>

p1 Event action box number (01 to 30)
p2 Event (ALARM)
p3 Action mode (EDGE, LEVL)
p4 Action

ALARM_ACK

Acknowledgement of
alarm status.

ALARM_RST

Alarm reset

TIMER_RST

Timer reset

MATH

Computation start/stop/

reset/clear/group reset

REPORT

Report start/stop

FLAG

Set flag to 1

p5 Auxiliary action information (for
p3=EDGE)

For p4=MATH

START

Computation starts.

STOP

Computation stops.

RESET

Computed data are reset.

CLEAR

Computed data are cleared.

RST_G01 to RST_G07

Computed data in the specified
group are clear.

For p4=REPORT

START

Report starts.

STOP

Report stops.

For p4=FLAG

F01 to F16:Specified flag number is set to 1.

p5 Auxiliary action information (for
p3=EDGE)

For p4=FLAG

F01 to F16:Specified flag number is set to 1.

Event function setting by a remote, relay, timer, or
match time event

Setting

SLp1, p2, p3, p4, p5, p6<terminator>

p1 Event action box number (01 to 30)
p2 Event (REMOTE, RELAY, TIMER,
MATCH_TIME)
p3 Auxiliary event information

For p2=REMOTE, contact number (1 to 12)

For p2=RELAY, the base unit + relay

number

For p2=TIMER, timer number (1 to 6)

For p2=MATCH_TIME, match time

number (1 to 3)

p4 Action mode (EDGE, LEVL)
p5 Action

ALARM_RST

Alarm reset

TIMER_RST

Timer reset

MATH

Computation start/stop/

reset/clear/group reset

REPORT

Report start/stop

FLAG

Set flag to 1

p6 Auxiliary action information

For p5=MATH

START

Computation starts.

STOP

Computation stops.

RESET

Computed data are reset.

CLEAR

Computed data are cleared.

RST_G01 to RST_G07

Computed data in the specified
group are clear.

For p5=REPORT

START

Report starts.

STOP

Report stops.

For p5=FLAG

F01 to F16:Specified flag number is set to 1.

Example

Set an event action to start coputation when an
alarm occurs in event action box 02.

SL02, ALARM, EDGE, MATH, START

Comments

• With an action as the start (event), another

action (action) can be executed automatically.

• Thirty types of event actions can be set.
• If the action mode is EDGE, the set action

continues even if the event action is over.

• If the action mode is set to LEVL , the set action

continues from the first event occurrence to the
next event occurrence.

• If the avtion mode is set to LEVL , the start/

stop/clear & start computation are disable.

• If the action is set to MATH, the edge and level

action cannot be set simultaneously.

• For details on an event/action, see the separate

manual (IMDP10001-61E).

SO

Sets the computational expression.

Mode

Operation mode

Setting

SOp1, p2, p3, p4, p5, p6<terminator>

p1

Channel for computation:
Stand-alone model: A01 to A30
Expandable model: A01 to A60

p2

Computation on/off (on/off)

p3

Computational expression
(up to 40 characters)

p4

Span left value (-9999999 to 99999999)

p5

Span right value (-9999999 to 99999999)

p6

Position of decimal point for span (0 to 4)

Example

Set the sum of channel numbers 001 and 002 to
channel A01 for computation. Set -10.0000 to
15.0000 for the span.

SOA01, ON, 001+002, -100000, 150000, 4

Comments

• This command only works with the optional

computation function or if a pulse module is
installed.

• For details on operators, see the Appendix at

the end of this manual.

• If you wish to omit either p4, p5, or p6, omit

them all together.

• If pulse modules are installed and there is no

computation function, TLOG.PSOM will be the
only valid operator.

SK

Sets the computational constants.

Mode

Operation mode

Setting

SKp1, p2 <terminator>

p1

Computational constant number:
Stand-alone model : K01 to K30
Expandable model : K01 to K60

p2

Constants

Example

Set 300 to a computational constant K10.

SKK10, 300

Comments

• This command is effective only with the

optional computation functions.

• Constant setting ranges are -1.0000E35 to

-1.0000E-35, 0, 1.0000E-35 to 1.0000E35.