3 data output request command – Yokogawa DA100 User Manual

Page 64

Advertising
background image

IM DA100-11E

6-12

If p2 is set to OFF, the relays with the setting
parameters of 1 are turned OFF, and those of 0
maintain the current condition.

• Always set p3 with four characters.
• The settings of bits 11 to 16 of p3 are ignored.

For the four-point alarm output relay module,
bits 5 to 16 are ignored.

6.3 Data Output Request Command

6.3

Data Output
Request Command

TS

Selects the output data.

Mode

All modes (A/D calibration data output is limited
to the A/D calibration mode only.)

Setting

TSp1<terminator>

p1

0 Measured data output
1 Setting data output
2 Unit data output
4 Report data output
5 System configuration data output
8 A/D calibration data output
9 Setting data output in setup mode

Comments

• Setting for p1=0, 1 or 2 is effective only in the

operation mode.

• Setting for p1=8 is effective only in the A/D

calibration mode.

• The setting, p1=4 is effective when the

instrument has the report function and one of
hourly, daily and monthly reports is ON.

FM

Selects the output format for measured
data.

Mode

Operation mode

Setting

FMp1, p2, p3<terminator>

p1

0 Outputs measured data in ASCII format.
1 Outputs measured data in binary format.
2 Outputs computed data in ASCII format.
3 Outputs computed data in binary format.

p2

First output channel (001 to 560)
First output computation channel (A01 to
A60)

p3

Last output channel (001 to 560)
Last output computation channel (A01 to
A60)

Comments

• Be sure to specify data to be output with the TS

command and execute “GET” or “ESC T”
before transmitting the FM command.

• The command selects the output format of

measured data, either ASCII or binary, and the
output channel.

• If there is no input channel recognized by the

DA100 among specified channels, a syntax
error occurs.

• For stand-alone models computaion channel

number is A01 to A30.

RF

Selects the output format of the report.

Mode

Operation mode

Setting

RFp1, p2, p3<terminator>

p1 0 Output hourly report data

1 Output daily report data
2 Output monthly report data
3 Output the status of the hourly/daily/

monthly data

p2 First channel for output (R01 to R60)
p3 Last channel for output (R01 to R60)

Comments

• This setting is effective when the instrument

has the report function.

• Before transmitting the RF command, be sure

to specify the data to output using the TS
command and execute “GET” or “ESC T.”