Overview and Specifications of RS-422-A/RS-485 Interface

3

3.5

RS-422-A/RS-485 Interface Parameter Setting
Procedure

Setting of the RS-422-A/RS-485 parameters must be carried out using the 4 dip switches located
next to the module connector.

1

2

3

4

SW1

Data length

Baud rate

ON

OFF

1

2

3

4

SW2

four-wire/two-wire
Stop bit

Parity

ON

OFF

1

2

3

4

SW3

Address (upper)

Minimum response time

ON

OFF

1

2

3

4

SW4

Address (lower)

ON

OFF

Baud rate (No.1 to 3 of SW1)

Baud rate

No.1

No.2

No.3

300

OFF

OFF

ON

600

OFF

ON

OFF

1200

OFF

ON

ON

2400

ON

OFF

OFF

4800

ON

OFF

ON

9600

ON

ON

OFF

Default Setting

19200

ON

ON

ON

38400

OFF

OFF

OFF

Data length (No.4 of SW1)

Data length

No.4

7

OFF

8

ON

Default Setting

Parity (No.1 to 2 of SW2)

Parity

No.1

No.2

None

OFF

OFF

ODD

OFF

ON

EVEN

ON

OFF

Default Setting

Stop bit (No.3 of SW2)

Stop bit

No.3

1

OFF

Default Setting

2

ON

Switch between four-wire/two-wire systems (No.4 of SW2)

four-wire/two-wire

No.4

four-wire

OFF

Default Setting

two-wire

ON