Xi sets the a/d integration time, Xq sets the filter, Xa performs the setting related to alarm – Yokogawa DA100 User Manual

Page 59: Xy sets the re-alarm for a re-failure, Xn sets and/or of the alarm output relay, Xd sets energizing or deenergizing, Xh sets the hold/non-hold, Xb sets the burnout

Advertising
background image

IM DA100-11E

6-7

Commands

6

Integration time: Equivalent to 50/60 Hz
Input module

Filter off

Filter on

10CH

0.5*

3

20CH

2

4

30CH

2

4

*: 2s if the power monitor module is installed
Integration time: 100 ms
Input module

Filter off

Filter on

10CH

4

12

20CH

5

15

30CH

6

20

XI

Sets the A/D integration time.

Mode

Setup mode

Setting

XIp1, p2<terminator>

p1

Subunit (0 to 5)

p2

Integration time (AUTO, 50 Hz, 60 Hz,
100 ms)

Example

Set the A/D integration time in subunit 0 to 50
Hz.

XI0, 50Hz

XQ

Sets the filter.

Mode

Setup mode

Setting

XQp1<terminator>

p1

ON

Filter on

OFF

Filter off

Example

Insert a filter in the input.

XQON

XA

Performs the setting related to alarm.

Mode

Setup mode

Setting

XAp1, p2, p3<terminator>

p1

Interval for limit of increasing rate-of-
change (1 to 15)

p2

Interval for limit of decreasing rate-of-
change (1 to 15)

p3

Alarm hysteresis (0.0 to 1.0)

Example

Set the interval for limit of increasing rate-of-
change to 10, the interval for the limit of the
decreasing rate-of-change to 10 and alarm
hysteresis to 0.5%.

Comments

• This command sets an interval to detect the rate-

of-change alarm and hysteresis.

• Set an interval using the measurement period

as the unit.

• Set the hysteresis with the percentage of the

measurement range or scaling range.

• The computation channel hysteresis is fixed to

0.

XY

Sets the re-alarm for a re-failure.

Mode

Setup mode

Setting

XYp1, p2<terminator>

p1

Reflash number (1 to 6)

p2

Off, subunit (I, 0 to 5) + relay number

Example

Set reflash relay 1 to relay module 1 connected to
slot 0 of the main unit.

XY1, I01

XN

Sets AND/OR of the alarm output relay.

Mode

Setup mode

Setting

XNp1, p2<terminator>

p1

Unit
I: Main unit (DA100)
0 to 5: Subunit

p2

Relay number to be set to AND (01 to 60)
NONE: All are OR.
01-XX (XX=01 to 60)
Relays whose numbers are 1 to XX are
set to AND.

Example

Have No. 1 of slot 0 to No. 10 of slot 2 in the
alarm output relay module connected to the main
unit be AND relay outputs.

XNI, I, 01-20

Comments

• Setting is effective only in the same unit.
• Set p2 with the first relay number (01=fixed)

to the last relay number. If all OR output is to
be set, set p2 to NONE.

An error will occur when alarm output module or
DI/DO module isn’t mounted to selected DA100
or DS400/DS600.

XD

Sets energizing or deenergizing.

Mode

Setup mode

Setting

XDp1, p2<terminator>

p1

Unit (I, 0 to 5) + Relay number (01 to 60)

p2

Selection of energizing/deenergizing

ENERG

Energizing

DE-EN

Deenergizing

Example

Set the relays of No. 1 in slot 0 to No. 10 in slot 5
of the relay module connected to subunit 5 to
energizing outputs.

XD501-60, ENERG

Comments

• If a successive number of output relays are to

be set, insert a minus sign (-) between the first
relay number and the last relay number, as
shown in the example. However, relays that
can be successively set are those in the same
subunit.

An error will occur when alarm output module or
DI/DO module isn’t mounted to selected DA100
or DS400/DS600.

XH

Sets the hold/non-hold.

Mode

Setup mode

Setting

XHp1<terminator>

p1

Output relay hold on/off

ON

Hold

OFF

Non-hold

Example

Hold the output state of an alarm output relay.

XHON

XB

Sets the burnout.

Mode

Setup mode

Setting

XBp1, p2<terminator>

p1

Channel number (001 to 560)

p2

Selection of burnout

OFF
UP

Upscale travelling beyond

the scale

DOWN

Downscale travelling

beyond the scale

Example

Set channels 01 to 10 of subunit 0 to upscale
burnout.

XB001-10, UP

Comments

• If channels are to be set successively, the setting

is effective only when they are in the same unit.

6.1 Setting Command