2 mx100 - specific error messages, Mx100 - specific error messages -3 – Yokogawa PC-Based MX100 User Manual

Page 1221

Advertising
background image

26-3

IM MX190-01E

Error Messages

26

26.2 MX100 - Specific Error Messages -

Below is a list of error values generated by the MX100, descriptions, and corrective
actions. The function CDAQMX::getLastError or getLastErrorMX can be used to

retrieve the value. With the extension API, a function (DAQMX100::getLastError or
lastErrorMX100) can be used to retrieve the value.

Value

Description

Corrective Action/Remarks

0

No error.

-

1

Not supported because the version is different.

Confirm the version number of MX100 and the API for the MX100/DARWIN.

2

The packet is too large.

Confirm the packet size.

3

Unknown request.

Confirm the request.

4

Inconsistent request.

Confirm the packet format.

6

The session number is incorrect.

Confirm the session number.

7

The FIFO number is incorrect.

Confirm the FIFO number.

8

Channel number is incorrect.

Confirm the channel number.

9

Data does not exist in the specified range.

Confirm the data number.

10

Configuration failed.

Confirm the module type and its status.

11

Failed due to the status.

Confirm the mode of the MX100. Executes the request when idle.

12

Invalid request against the DO.

Confirm the output setting for DO.

13

No CF card.

Insert a CF card in the drive.

14

The CF card cannot be formatted (the CF card is present).

The CF card may be out of order. Replace the CF card.

23

Initial balancing not correctly performed. Check the module’s installation

conditions, then perform initial balancing again. If the error occurs even after

recalibrating, please contact your nearest Yokogawa representative.

255

Communication error.

Communication error. Please contact your nearest Yokogawa representative.

256

Other error.

Other error. Please contact your nearest Yokogawa representative.