Setcommx – Yokogawa PC-Based MX100 User Manual

Page 308

Advertising
background image

5-50

IM MX190-01E

setCOMMX

Syntax

int setCOMMX(DAQMX daqmx, int iRangeCOM, int startChNo, int
endChNo, int spanMin, int spanMax, int scaleMin, int scaleMax,
int scalePoint);

Declaration

Public Declare Function setCOMMX Lib "DAQMX" (ByVal daqmx As
Long, ByVal iRangeCOM As Long, ByVal startChNo As Long, ByVal
endChNo As Long, ByVal spanMin As Long, ByVal spanMax As Long,
ByVal scaleMin As Long, ByVal scaleMax As Long, ByVal
scalePoint As Long) As Long

Parameters

daqmx

Specify the device descriptor.

iRangeCOM

Specify the communication range from the range type.

startChNo

Specify the start channel number.

endChNo

Specify the end channel number.

spanMin

Specify the span minimum.

spanMax

Specify the span maximum.

scaleMin

Specify the scale minimum.

scaleMax

Specify the scale maximum.

scalePoint

Specify the decimal point position for scaling.

Description

Sets the specified channel range to the communication range.

• If the minimum and maximum values of the span are equal, the span is

considered to be omitted.

• If the minimum and maximum values of the scale are equal, the scale is

considered to be omitted.

• The setup data is retrieved collectively, changed, and sent collectively.
• Channels from unsupported modules are ignored.

• The alarm setting is initialized.

Return value

Returns an error number.

Errors:
Not descriptor

No device descriptor.

Reference

CDAQMX::getMXConfig
CDAQMX::setMXConfig
CDAQMXConfig::setCOM
CDAQMXConfig::setScalling

5.1 Details of Functions - MX100 (Visual C/Visual Basic) -