HT instruments SOLAR I-V User Manual

Page 33

Advertising
background image

I-V400 - SOLAR I-V

EN - 31

22.

At any time it will be possible to analyze the current
recording status by pressing the MENU key. The following
information will be shown:

 Starting date and time of recording
 The value set for the integration period
 The number of periods elapsed from the beginning of the

recording

 The remaining memory capacity for recording

Press the ESC key to exit the screen

15/05/10 15:35:00

S t a r t

1 4 / 0 2 / 0 0 1 7 : 1 8 : 0 0
P e r i o d : 5 s

I P N u m b e r 6 1

R e c . T i m e

0 d 1 h

R e c . R u n n i n g

Select

M P P

23. Now it is possible to bring the unit SOLAR-02 near the PV strings to measure irradiation and

temperature by means of the relevant probes. When the distance between unit SOLAR-
02 and MPP300 does not allow the RF connection, on the display of SOLAR-02 the
symbol “

” flashes for approx. 30s and then disappears. Unit MPP300 steadily

searches for the RF connection with unit SOLAR-02.

24. Position the reference cell onto the surface of the PV modules. Please refer to the relevant

User Manual for a correct assembly.


25. Put the temperature sensor in contact with the rear side of the module and fasten it with

some tape; prevent touching it with your fingers (as this could alter the measure).


26. Wait for a few seconds to allow the probes to reach a steady measure and then connect the

irradiation probe to input PYRA/CELL and the temperature probe to input TEMP of unit
SOLAR-02.


27. Wait for the message “READY” to appear on the display of SOLAR-02 to indicate that the

unit has detected the data with solar irradiation > minimum threshold set (see § 5.1.5).


28. With the message “READY” shown on the display, wait for approximately 1 minute in

order to take a certain number of samples.


29. Disconnect the irradiation and temperature probes from unit SOLAR-02 and bring the unit

near unit MPP300. Bring the main unit SOLAR I-V near MPP300 too. The three units must
be near each other (max distance 1m).


30. The main unit SOLAR I-V must be in EFF mode; if no flashing symbol “

” appears, press

key

 to activate the RF connection search again.


31. Press key

 on SOLAR-02 to activate the RF connection again. Consequently, the main

unit will show the message “active radio connection”.