Caution, I-v400 - solar i-v – HT instruments SOLAR I-V User Manual

Page 37

Advertising
background image

I-V400 - SOLAR I-V

EN - 35

19. Connect the meter to the module/string under test as shown in Fig. 7a. In particular,

connect the negative output pole of module/string to P1, C1 input terminals and the
positive output pole of module/string to P2, C2 input terminals

Fig. 7a: Instrument connection to module/string FV Fig. 7b: Positioning of inclinometer M304

CAUTION

The method used by the instrument meter for output VDC and IDC
measurements of PV module/string is the “4-wire”. Therefore, it is possible to
use also test cables connected to P1, C1, P2, C2 inputs of different length
without performing any calibration of cable resistance. It is recommended to
use cables with a §

4mm

2

20. After connection to the plant, the real time values of

parameters are shown by meter:
 Vdc = DC output voltage of PV module/string
 Irr = Irradiance value measured by sensor
 Tc = Value of module temperature

15/05/10 15:34:26

V d c = 3 6 7 V

I r r = 1 0 4 5 W / m 2

T c = 4 5 ° C

Module: SUNPOWER 210

Select

I - V

CAUTION

At the press of GO/STOP key some different error messages can be
displayed by the meter (see § 6.4) and, due of this, the test cannot start.
Check and remove, if possible, this error message before start the test

21. Press GO/STOP key to start the test. If none of the

previous error messages are detected, the message
Measuring…” is shown on the display for some seconds,
depending on the level of power during test.

15/05/10 15:34:26

V d c = 3 6 7 V

I r r = 1 0 4 5 W / m 2

Tc = 45 °C


Module: SUNPOWER 210

Measuring…

Select

I - V

Advertising