Caution – HT instruments SOLAR I-V User Manual

Page 56

Advertising
background image

I-V400 - SOLAR I-V

EN - 54

6.3.4. Fast check IVCK with irradiance measurement


CAUTION

 The maximum voltage among inputs P1, P2, C1 and C2 is 1000V DC. Do not

measure voltages exceeding the limits expressed in this manual.

 The maximum current allowable for the instrument is 10A. Do not effect tests in

parallel on FV module strings.

 Never effect tests on modules or FV strings connected to DC/AC converter.

1. Turn on the instrument pressing ON/OFF
2. Irradiance measurement can be carried out just through the following modes:

 Measurement through reference cell directly connected to I-V400 or SOLAR I-V
 Measurement through reference cell connected to SOLAR-02 under RF to I-V400 or

SOLAR I-V

Check that the remote unit SOLAR-02 setting is consistent with the type of
measurement to be effected (see §5.1.4).

3. Check the minimum irradiance value set in the “irradiance” section (see § 5.1.5).
4. Go back to main MENU and select “I-V
5. Select “I-V” and press ENTER to enter the FV module performance measurement section.

Generally when selecting I-V on general menu the instrument automatically shows the last
mode under use (I-V or IVCK).

6. In case the current mode is not IVCK, press ENTER,

select “Measurement ” by means of arrow keys
(

,). Use the arrow key  to enter the internal

submenu, select “IV Check” and confirm pressing
ENTER to start up the initial screen of fast check IVCK

15/05/10 15:34:26

V d c = 0 . 0 V

I r r = 0 W / m 2

T c = - - - ° C

Module: SUNPOWER 210

F e a t u r e

I V

I m p

M e a s u r e m e n

t R S

M i s

I V C h e c k

Selezione

I - V

7. Check the preliminary settings based on descriptions of § 6.3.2
8. Connect the instrument to the module/string under test as shown in the following

picture. In particular connect the negative pole of the module/string to terminals P1, C1
and it positive pole to terminals P2, C2.

Caption:

P1: Black

cable

P2: Blue

cable

C1: Green cable

C2: Red cable

1:

Module or FV string

2:

Reference cell

3: Temp probe (if

required)

4 Remote unit SOLAR-02

Fig. 14: Instrument’s connection for

IVCK tests with direct measurement

of Irrad/Temp

Fig. 15: Instrument’s connection for

IVCK tests with measurement of

Irrad/Temp through SOLAR-02