4 table of settable functions – KROHNE IFC 110 Converter User Manual

Page 32

Advertising
background image

Sect. 4.4

Part B IFC 110 F Signal converter

32

IFC 110 F

05/2003

4.4

Table of settable functions


Abbreviations used:

A1, A2 Status outputs

P (P2) Pulse output (2nd pulse output A1)

(A1 can also be 2nd pulse output A1)

P

max

= F

max

/Q

100%

C1, C2 Control inputs

P

min

= F

min

/Q

100%

D1, D2 Status outputs

Q

Current flow rate

DN

Meter size, nominal size

Q

100%

100% flow rate = full-scale range

F

max

= ½ x pulse width (s) for

≤ 50 Hz

≤ 10 kHz if ”AUTO” or ”SYM.” are selected in Q

max

= /4 DN² x v

max

(= max. full-scale range

subfunction ”PULSWIDTH”

Q

100%

at v

max

= 12 m/s or 40 ft/s)

F

min

= 10 pulses/h

F

M

Conversion factor volume for any unit,

Q

min

= /4 DN² x v

min

(= min. full-scale range

see Fct. 3.05 ”FACT. VOL.”

Q

100%

at v

min

= 0.3 m/s or 1 ft/s)

F

T

Conversion factor time for any unit,

SMU

Low-flow cutoff for I and P

see Fct. 3.05 ”FACT. TIME”

v

Flow velocity

GK

Flow sensor constant

v

max

Maximum flow velocity (12 m/s or 40 ft/s) at Q

100%

I

Current output

v

min

Minimum flow velocity (0.3 m/s or 1 ft/s) at Q

100%

I

0%

Current at 0% flow rate

F/R

Forward/reverse flow in F/R measuring mode

I

100%

Current at 100% flow rate


Fct. Text

Description

and

setting

1.0

OPERATION

Operating menu

FULL SCALE

Full-scale range for flow rate Q

100%

Selection of unit

• m³/h

• Liter/Sec

• US.Gal/min

• user unit, factory setting ”Liter/h” or ”US MGal/day” (see Fct. 3.05)

Press

→ key to change to numerical setting

Setting

ranges

The range depends on the nominal width (DN) and the

flow velocity (v):

Q

min

= DN² x v

min

Q

max

= DN² x v

max

Nominal width/meter size

v

min

= 0.3 m/s (1 ft/s)

v

max

= 12 m/s (40 ft/s)

● DN 2.5–1200 /

1

/

10

”–48”:

0.0053

– 48 860 m³/h

0.0237

– 218 560 US.Gal/min

● DN 1300–3000 / 52”–120” 1435

– 305 360 m³/h

(see Section 8.6)

6415

– 1 366 000 US.Gal/min

Press

↵ key to return to Fct. 1.01 FULL SCALE

→ VALUE P

Pulse value for pulse output P (Fct. 1.06 ”VALUE P”) and/or

and/or

for the 2nd pulse output A1 (Fct. 1.07 ”VALUE P2”) has been changed.

→ VALUE P2

With the ”old” pulse values the output frequency (F) would have

been exceeded or would not have been reached.

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Check new values!

1.02 TIMECONST. Time

constant

Selection: ● ALL (applies to display and all outputs)

● ONLY I (only display, current and status outputs)

Press

↵ key to change to numerical setting.

Range:

● 0.2 – 99.9 Sec

Press

↵ key to return to Fct. 1.02 TIMECONST.

1.03

L.F. CUTOFF

Low-flow cutoff (L.F. CUTOFF)

● OFF (fixed tripping points: ON = 0.1% / OFF = 0.2%)

● PERCENT (variable tripping points)

ON

OFF

1 – 19%

2 – 20%

Press

→ key to change to numerical setting.

Note: the cutoff ”OFF” value must be greater than the cutoff ”ON” value.

Press

↵ key to return to Fct. 1.03 L.F. CUTOFF.

π

4

π

4

π

4

π

4