KROHNE IFC 110 Converter User Manual

Page 47

Advertising
background image

Part B IFC 110 F Signal converter Sect. 5.10

05/2003

IFC 110 F

47


Characteristic of status outputs

Switch open

Switch closed

OFF (switched off)

no function

ON (e.g. operation indicator)

power supply OFF

power supply ON

SIGN I (F/R mode)

forward flow

reverse flow

SIGN P/P2 (F/R mode)

forward flow

reverse flow

FULL SCALE (full-scale indicator)

inactive active

AUTO. RNG. (autom. range change)

high range

low range

OVERFL. I (I range exceeded)

current output O.K.

cur. output range exceeded

OVERFL. P/P2 (P range exceeded)

pulse output O.K.

pulse output range exceeded

ALL ERROR (all errors)

error no

error

FATAL.ERROR (only fatal errors)

error no

error

INVERS A1: status output A2 . . .

when A1 is closed

when A1 is open

INVERS D1: status output D2 . . .

when D1 is closed

when D1 is open

EMPTY PIPE (empty tube
identification option)

when measuring tube
is empty

when measuring tube
is full


For factory settings please refer to Section 2.7.

5.10 Control inputs C1 and C2


Fct. 1.11 CONTROL C1

Fct. 1.12 CONTROL C2

Press

key

and/or

Press

key


Select function for the control inputs, press

orkey

OFF

(switched off, no function)

OUTP. HOLD

(hold output values)

Functions also act on

OUTP. ZERO

(set outputs to ”min. values”)

}

display and totalizer

TOTAL. RESET (reset totalizer)

ERROR. RESET (acknowledge/delete error messages)

EXT. RNG.

(external range change for automatic range change, see Sect. 5.20.

Setting

range 5 - 80 PERCENT = low to high range ratio

1:20 to 1:1.25, value must be greater than that of Fct. 1.03 L.F. CUTOFF)


Press

key to change to numerical setting, 1st number (cursor) flashes.

Change flashing number (cursor) with keys

and ↓ . Useandkeys to shift cursor

1 place to right or left.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.

Press

key to return to Fct. 1.11 CONTROL C1 or to Fct. 1.12 CONTROL C2.


Please refer to Section 2.7 for factory settings.

Connection diagram see Section 2.6.

Advertising