Part C Special applications, functional checks, service, and order numbers Sect. 6.1

05/2003

IFC 110 F

53

5.19 Limit

switches


Fct. 1.07 - 1.10 Status outputs A1, A2, D1 or D2
(Define operating mode of output terminals A1, see Section 5.18)
Press

→ key

Press

↑ key as often as required to set one of the status outputs to ”TRIP. POINT”


Press

→ key to change to ”Characteristic” (flow direction).


Select:

• + DIR.

• – DIR.

Select with

↑ or ↓ keys

• 2 DIR.

}


Press

↵ key to change to numerical setting, 1st number (cursor) flashes.

Change flashing number (cursor) with keys

↑ and ↓. Use → and ← keys to shift cursor

1 place to right or left.

• Display: XXX – YYY


• Setting ranges: XXX value = 0 – 150% of Q

100%

YYY value = 0 – 150% of Q

100%

hysteresis

≥ 1% (= difference between XXX and YYY values)


• Switching behaviour (NO/NC contact) and hysteresis are adjustable.


NC contact XXX value > YYY value

NC contact XXX value < YYY value

Switch closes when flow exceeds XXX value

Switch opens when flow exceeds YYY value

Example: XXX = 55%

Example: XXX = 45%

YYY = 45%

YYY = 55%

hysteresis = 10%

hysteresis = 10%


Please note:

if two status outputs (e.g. D1 and D2) are activated

it is possible to have e.g. min. and max. values signalled.