Part C Special applications, functional checks, service, and order numbers Sect. 7.5

05/2003

IFC 110 F

73

Group I

Faults / Symptoms

Cause

Remedial action

I 3

22 mA are available at

Range of current output I is

Check instrument parameters

current output (fault current)

exceeded

and correct if necessary

(see Sect. 2.2 and 5.7) or con-

sult KROHNE Service, having

first

noted

down

hardware

information and error status,

see Sect. 7.3, Fct. 2.02.

I 4

22 mA are available at

Fatal Error

Replace signal converter or

current output (fault current)

consult KROHNE Service,

and red LED flashes

having first noted down hard-

ware

information

and

error

status, see Sect. 7.3, Fct. 2.02

I 5

Unsteady display

Electric conductivity of

Increase time constant

process liquid too low

(see Sect. 5.2, Fct. 1.2).

Also refer to Sect. 6.7.

I 6

Receiver instruments

Control input C1 or C2 is

Change setting (see Sect. 5.10,

indicate ”constant value”

set to ”Hold outputs” and

Fct. 1.11 and 1.12), or

is activated

deactivate control input.

I 7

Jumping current values

Current output is set to

Change hysteresis or tripping

automatic range change

ranges, see Sect. 5.20.

I 8

F/R-Mode:

Different ranges set for

Change setting,

different displays for identical

”forward flow” and

see Sect. 5.15, Fct. 1.05

flow volumes in both

”reverse flow”

”Rev. range”.

directions

I 9

Receiver instruments

Control input C1 or C2 is set

Change setting (see

indicate ”min. values”

to ”Zero outputs” or ”Hold

Sect. 5.10, Fct. 1.11 and 1.12)

outputs” and is activated

or deactivate control input.