West Control Solutions KS 92-1 User Manual

Page 14

Advertising
background image

g

Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3, the è-key or the Ò-key.
Configuration, see page 37:

ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.

Operation

Error list / Maintenance manager

14

KS 90-1 / KS 92-1

Name

Description

Cause

Possible remedial action

SSr

Heating current

short circuit

(SSR)

- Current flow in heating

circuit with controller off

- SSR defective

- Check heating current circuit
- If necessary, replace solid-state relay

LooP

Control loop

alarm (LOOP)

- Input signal defective or not

connected correctly

- Output not connected

correctly

- Check heating or cooling circuit
- Check sensor and replace it, if

necessary

- Check controller and switching

device

AdA.H

Self-tuning

heating alarm
(ADAH)

- See Self-tuning heating

error status

- see Self-tuning heating error status

AdA.C

Self-tuning

heating alarm

cooling (ADAC)

- See Self-tuning cooling

error status

- see Self-tuning cooling error status

dAC

DAC-Alarm

Actor error

see errorstatus DAC-function

LiM.1/

2/3

stored limit

alarm 1/2/3

- adjusted limit value 1/2/3

exceeded

- check process

Inf.1

time limit value

message

- adjusted number of

operating hours reached

- application-specific

Inf.2

duty cycle

message
(digital ouputs)

- adjusted number of duty

cycles reached

- application-specific

E.5

Internal error in

DP module

self-test errorinternal

communication interrupted

Switch on the instrument

againContact PMA service

dp.1

No access by bus

master

bus errorconnector

problemno bus connection

Check cableCheck connectorCheck

connections

dp.2

Faulty

configuration

Faulty DP configuration

telegram

Check DP configuration telegram in

master

dp.3

Inadmissible

parameter

setting telegram

sent

Faulty DP parameter

setting telegram

Check DP parameter setting

telegram in master

dp.4

No data

communication

Bus errorAddress

errorMaster stopped

Check cable connectionCheck

addressCheck master setting