Othr – West Control Solutions KS 92-1 User Manual

Page 40

Advertising
background image

Configuration level

Configuration parameters

40

KS 90-1 / KS 92-1

Name

Value range Description

Default

Err.r

Reset of all error list entries

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

6

Ò - key switches

Pid.2

Switching of parameter set (Pb, ti, td)

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

I.Chg

Switching of the actual process value between Inp1 and X2

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

di.Fn

Function of digital inputs (valid for all inputs)

0

0

direct

1

inverse

2

toggle key function

fDI1
fDI2
fDI3

Forcing di1/2/3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

othr

Name

Value range

Description

Default

bAud

Baudrate of the interface (only visible with OPTION)

2

0

2400 Baud

1

4800 Baud

2

9600 Baud

3

19200 Baud

Addr

1...247

Address on the interace (only visible with OPTION)

1

PrtY

Data parity on the interface (only visible with OPTION)

1

0

no parity (2 stop bits)

1

even parity

2

odd parity

3

no parity (1 stopbit)

dELY

0...200

Delay of response signal [ms] (only visible with OPTION)

0