West Control Solutions KS 92-1 User Manual

Page 42

Advertising
background image

Configuration level

Configuration parameters

42

KS 90-1 / KS 92-1

Name

Value range

Description

Default

IExo

Block extended operating level (only visible with BlueControl!)

0

0

Released

1

Blocked

ILat

Suppression error storage (visible only with BlueControl

®

!) 0

0

No:

error message remain in the error list until

acknowledgement.

1

Yes

alarms are deleted from the error list as soon as

corrected

Pass

OFF...9999

Password (only visible with BlueControl!)

OFF

IPar

Block parameter level (only visible with BlueControl!)

0

0

Released

1

Blocked

ICnf

Block configuration level (only visible with BlueControl!)

0

0

Released

1

Block

ICal

Block calibration level (only visible with BlueControl!)

0

0

Released

1

Blocked

CDis3

Display3controlleroperatinglevel (onlyvisiblewithBlueControl!)

2

0

No value / only text

1

Display of value

2

Output value as bargraph

3

Control deviation as bargraph

4

Process value as bargraph

TDis3

2...60

Display3displayalternationtime[s] (onlyvisiblewithBlueControl!)

10

T.dis3

8 Zeichen

Text display 3 (only visible with BlueControl!)

T.InF1

8 Zeichen

Text Inf.1 (only visible with BlueControl!)

T.InF2

8 Zeichen

Text Inf.2 (only visible with BlueControl!)

Lin

(only visible with BlueControl

â

Name

Value range

Description

Default

Lin

Linearization for inputs INP1 or INP3
Access to this table is always with selection special

thermocouple for

InP.1 or InP.3or with setting

S.Lin = 1: special linearization for linearization.

Default: KTY 11-6 (0...4,5 kOhm)

U.LinT

Unit of linearization table

0

0

No unit

1

In Celsius [°C]

2

In Fahrenheit [°C]

In.1

-999.0..99999

Input value 1
The signal is in [µV] or in [[] dependent of input type

1036

Ou.1

0,001...9999

Output value 1
Signal assigned to

In.1

-49,94