West Control Solutions KS 92-1 User Manual
Page 42

Configuration level
Configuration parameters
42
KS 90-1 / KS 92-1
Name
Value range
Description
Default
IExo
Block extended operating level (only visible with BlueControl!)
0
0
Released
1
Blocked
ILat
Suppression error storage (visible only with BlueControl
®
!) 0
0
No:
error message remain in the error list until
acknowledgement.
1
Yes
alarms are deleted from the error list as soon as
corrected
Pass
OFF...9999
Password (only visible with BlueControl!)
OFF
IPar
Block parameter level (only visible with BlueControl!)
0
0
Released
1
Blocked
ICnf
Block configuration level (only visible with BlueControl!)
0
0
Released
1
Block
ICal
Block calibration level (only visible with BlueControl!)
0
0
Released
1
Blocked
CDis3
Display3controlleroperatinglevel (onlyvisiblewithBlueControl!)
2
0
No value / only text
1
Display of value
2
Output value as bargraph
3
Control deviation as bargraph
4
Process value as bargraph
TDis3
2...60
Display3displayalternationtime[s] (onlyvisiblewithBlueControl!)
10
T.dis3
8 Zeichen
Text display 3 (only visible with BlueControl!)
T.InF1
8 Zeichen
Text Inf.1 (only visible with BlueControl!)
T.InF2
8 Zeichen
Text Inf.2 (only visible with BlueControl!)
Lin
(only visible with BlueControl
â
Name
Value range
Description
Default
Lin
Linearization for inputs INP1 or INP3
Access to this table is always with selection special
thermocouple for
InP.1 or InP.3or with setting
S.Lin = 1: special linearization for linearization.
Default: KTY 11-6 (0...4,5 kOhm)
U.LinT
Unit of linearization table
0
0
No unit
1
In Celsius [°C]
2
In Fahrenheit [°C]
In.1
-999.0..99999
Input value 1
The signal is in [µV] or in [[] dependent of input type
1036
Ou.1
0,001...9999
Output value 1
Signal assigned to
In.1
-49,94