5.3 Input scaling

When using current, voltage or resistance signals as input variables for

InP.1,

InP.2 or/and InP.3 scaling of input and display values at parameter setting le-
vel is required. Specification of the input value for lower and higher scaling point
is in the relevant electrical unit (mA / V /

W).

5.3.1 Input

Inp.1 and InP.3

g

Parameters

InL.x , OuL.x, InH.x and OuH.x are only visible if

ConF / InP.x / Corr = 3 is chosen.
In addition to these settings,

InL.x and InH.x can be adjusted in the range

(0...20mA / 0...10V /

W) determined by selection of S.tYP .

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for

InL.x and OuL.x and for InH.x and

OuH.x must have the same value.

g

Input scaling changes at calibration level (r page 61) are displayed by input
scaling at parameter setting level. After calibration reset (

OFF), the scaling

parameters are reset to default.

5.3.2 Input

InP.2

In addition to these settings,

InL.2 and InH.2 can be adjusted in the range

(0...20/ 50mA/

W) determined by selection of S.tYP.

Parameter setting level

Input scaling

60

KS 90-1 / KS 92-1

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x

S.tYP

Input signal

InL.x

OuL.x

InH.x

OuH.x

30

(0...20mA)

0 … 20 mA

0

any

20

any

4 … 20 mA

4

any

20

any

40

(0...10V)

0 … 10 V

0

any

10

any

2 … 10 V

2

any

10

any

S.tYP

Input signal

InL.2

OuL.2

InH.2

OuH.2

30

0 … 20 mA

0

any

20

any