5.3 Input scaling
When using current, voltage or resistance signals as input variables for
InP.1,
InP.2 or/and InP.3 scaling of input and display values at parameter setting le-
vel is required. Specification of the input value for lower and higher scaling point
is in the relevant electrical unit (mA / V /
W).
5.3.1 Input
Inp.1 and InP.3
g
Parameters
InL.x , OuL.x, InH.x and OuH.x are only visible if
ConF / InP.x / Corr = 3 is chosen.
In addition to these settings,
InL.x and InH.x can be adjusted in the range
(0...20mA / 0...10V /
W) determined by selection of S.tYP .
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for
InL.x and OuL.x and for InH.x and
OuH.x must have the same value.
g
Input scaling changes at calibration level (r page 61) are displayed by input
scaling at parameter setting level. After calibration reset (
OFF), the scaling
parameters are reset to default.
5.3.2 Input
InP.2
In addition to these settings,
InL.2 and InH.2 can be adjusted in the range
(0...20/ 50mA/
W) determined by selection of S.tYP.
Parameter setting level
Input scaling
60
KS 90-1 / KS 92-1
mA/V
phys.
quantity
mA / V
phys. quantity
OuH.x
OuL.x
InH.x
InL.x
S.tYP
Input signal
InL.x
OuL.x
InH.x
OuH.x
30
(0...20mA)
0 … 20 mA
0
any
20
any
4 … 20 mA
4
any
20
any
40
(0...10V)
0 … 10 V
0
any
10
any
2 … 10 V
2
any
10
any
S.tYP
Input signal
InL.2
OuL.2
InH.2
OuH.2
30
0 … 20 mA
0
any
20
any