Configuration parameters
Name
Value range Description
Default
FAIL
Behaviour at sensor break
1
0
controller outputs switched off
1
y = Y2
2
y = mean output. The maximum permissible output can be
adjusted with parameter
Ym.H. To prevent determination of
inadmissible values, mean value formation is only if the
control deviation is lower than parameter
L.Ym.
rnG.L
-1999...9999
X0 (start of control range) 1
-100
rnG.H
-1999...9999
X100 (end of control range) 1
1200
CYCL
Characteristic for 2-point- and 3-point-controllers
0
0
standard
1
water cooling linear (siehe Seite 45)
2
water cooling non-linear
3
with constant cycle
tunE
Auto-tuning at start-up
0
0
At start-up with step attempt, at set-point with impulse attempt
1
At start-up and at set-point with impulse attempt. Setting for
fast controlled systems (e.g. hot runner control)
2
Always step attempt at start-up
Strt
Start of auto-tuning
0
0
Manual start of auto-tuning
1
Manual or automatic start of auto-tuning at power on or
when oscillating is detected
Adt0
Optimization of T1, T2 (only visible with BlueControl!)
0
0
Automatic optimization
1
No optimization
1 rnG.L and rnG.H are indicating the range of control on which e.g. the
self-tuning is refering
InP.1
Name
Value range Description
Default
I.fnc
INP1 function selection
7
0
No function (following INP data are skipped)
1
Heating current input
2
External set-point
SP.E (switch-over -> LOGI/ SP.E)
3
Position feedback Yp
4
Second process value x2 (ratio, min, max, mean)
5
External positioning value Y.E (switch-over r
LOGI / Y.E)
6
No controller input (e.g. limit signalling instead)
7
Process value x1
S.tYP
Sensor type selection
1
0
thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
thermocouple type J (-100...1200°C) , Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil